| Plan dimensions | 30.0 m ÃÂà18.0 m | | Bay sizes | 6.0 m ÃÂà9.0 m (5 bays ÃÂà2 bays) | | Floor-to-floor height | 4.0 m (ground to level 2), 3.6 m (level 2 to roof) | | Roof | Flat roof, steel deck on OWSJ | | Floors | 75 mm concrete on 38 mm steel deck | | Lateral system | Concentrically braced frames (HSS) | | Seismic | Toronto: S_a(0.2) = 0.39, S_a(1.0) = 0.13 | | Importance category | Normal (I_E = 1.0) | | Site class | C (very dense soil, 360 âÃÂä v_s < 760 m/s) |
Material Specifications
| Component | Grade | Fy (MPa) | Fu (MPa) |
|---|---|---|---|
| Beams and girders | 350W | 350 | 450 |
| Columns | 350W | 350 | 450 |
| Braces | HSS 350W | 350 | 450 |
| Bolts | A325M | — | 830 |
| Welds | E49XX | — | 490 |
| Steel deck | 38 mm | 230 | — |
| Concrete (deck) | 25 MPa | — | — |
Gravity Loads
Per NBCC 2020 — Ontario:
Dead Loads
| Element | Load (kPa) |
|---|---|
| Roof: steel deck + roofing | 0.30 |
| Roof: mechanical allowance | 0.15 |
| Floor: steel deck + concrete | 2.40 |
| Floor: ceiling + services | 0.30 |
| Floor: partitions (allowance) | 1.00 |
| Cladding (along perimeter) | 1.5 kN/m |
Live Loads
| Occupancy | Load (kPa) |
|---|---|
| Office (floors) | 2.4 |
| Corridors | 4.8 |
| Roof (snow) | 1.44 |
| Roof (construction) | 1.0 |
Snow load for Toronto: S_s = 1.2 kPa (ground), C_b = 1.0, S = I_s ÃÂÃÂ S_s ÃÂÃÂ (C_b ÃÂÃÂ C_w ÃÂÃÂ C_s ÃÂÃÂ C_a) = 1.0 ÃÂÃÂ 1.2 ÃÂÃÂ 1.0 ÃÂÃÂ 1.0 ÃÂÃÂ 1.0 ÃÂÃÂ 1.0 ÃÂÃÂ 1.2 = 1.44 kPa.
Gravity Beam Design — Typical Floor Beam
Given: Simply supported floor beam spanning 9.0 m at 3.0 m tributary width (beams at 3.0 m centres). Floor: 75 mm concrete on 38 mm steel deck. Composite action with shear studs.
Step 1 — Factored Loads:
Dead: w_D = (2.40 + 0.30 + 1.00) ÃÂÃÂ 3.0 = 11.1 kN/m Live: w_L = 2.4 ÃÂÃÂ 3.0 = 7.2 kN/m (office, reducible per NBCC)
Live load reduction (tributary area = 9.0 ÃÂà3.0 = 27 mÃÂò > 20 mÃÂò): Reduction = 0.3 + sqrt(9.8/27) = 0.3 + 0.603 = 0.903. Live = 0.903 ÃÂà2.4 = 2.17 kPa. w_L_red = 2.17 ÃÂà3.0 = 6.5 kN/m
Factored load (NBCC ULS 1): w_f = 1.25 ÃÂÃÂ 11.1 + 1.5 ÃÂÃÂ 6.5 = 13.88 + 9.75 = 23.63 kN/m
Step 2 — Bending Moment and Shear:
M_f = w_f ÃÂàLÃÂò / 8 = 23.63 ÃÂà9.0ÃÂò / 8 = 239.3 kNÃÂ÷m V_f = w_f ÃÂàL / 2 = 23.63 ÃÂà9.0 / 2 = 106.3 kN
Step 3 — Section Selection (Composite Beam):
Try W360ÃÂÃÂ45 (350W): A = 5,730 mmÃÂò, d = 350 mm, b_f = 170 mm, t_f = 13.0 mm, t_w = 7.2 mm, I_x = 121 ÃÂà10âÃÂö mmâÃÂô, S_x = 694 ÃÂà10ÃÂó mmÃÂó (non-composite).
Composite section properties (effective slab width = min(L/4, beam spacing) = min(9,000/4, 3,000) = 2,250 mm): Concrete flange: 2,250 mm wide ÃÂÃÂ 75 mm thick (above deck ribs). Assume 50% composite action with 19 mm shear studs at 300 mm centres (12 studs per half-span).
Approximate composite M_r (50% shear connection): M_r âÃÂàphi ÃÂà(0.85 ÃÂàA_s ÃÂàFy ÃÂà(d/2 + h_c - a/2), where a is the depth of the concrete compression block.
For W360ÃÂÃÂ45 with 50% composite: M_r,comp âÃÂà390 kNÃÂ÷m (calculated per CSSBI design tables).
M_f = 239.3 âÃÂä 390 kNÃÂ÷m. OK. (Ratio = 0.61)
Step 4 — Deflection Check:
delta_LL = 5 ÃÂàw_L_red ÃÂàLâÃÂô / (384 ÃÂàE ÃÂàI_x,comp) I_x,comp (50% transformed) âÃÂà240 ÃÂà10âÃÂö mmâÃÂô delta_LL = 5 ÃÂà6.5 ÃÂà9,000âÃÂô / (384 ÃÂà200,000 ÃÂà240 ÃÂà10âÃÂö) = 11.6 mm
delta_allow = L/360 = 9,000/360 = 25.0 mm
delta_LL = 11.6 âÃÂä 25.0 mm. OK.
Result: W360ÃÂÃÂ45 composite floor beam with 12-19 mm shear studs per half-span (300 mm centres). Satisfies CSA S16:24 for composite beam design.
Lateral Load Design — Braced Frame
Seismic base shear per NBCC 2020:
V = S(T_a) ÃÂÃÂ M_v ÃÂÃÂ I_E ÃÂÃÂ W / (R_d ÃÂÃÂ R_o)
T_a = 0.05 ÃÂÃÂ h_n^(3/4) = 0.05 ÃÂÃÂ 7.6^(3/4) = 0.05 ÃÂÃÂ 4.66 = 0.233 s
S(0.233) âÃÂàS_a(0.2) = 0.39 (short period). M_v = 1.0.
R_d = 2.0, R_o = 1.3 (moderately ductile CBF). Total R = 2.6.
Seismic weight W: Roof = (0.30 + 0.15) ÃÂÃÂ 30 ÃÂÃÂ 18 = 243 kN. Floor = (2.40 + 0.30 + 1.00 + 0.25 ÃÂÃÂ 2.4) ÃÂÃÂ 30 ÃÂÃÂ 18 = 4.30 ÃÂÃÂ 540 = 2,322 kN. Cladding: 1.5 ÃÂÃÂ (30 + 18) ÃÂÃÂ 2 ÃÂÃÂ 7.6 = 1,094 kN.
W_total âÃÂà243 + 2,322 + 1,094 = 3,659 kN (total seismic weight)
V = 0.39 ÃÂÃÂ 1.0 ÃÂÃÂ 1.0 ÃÂÃÂ 3,659 / 2.6 = 549 kN
Distribute to roof and floor per NBCC: F_roof = 549 ÃÂÃÂ (243 ÃÂÃÂ 7.6) / (243 ÃÂÃÂ 7.6 + 2,322 ÃÂÃÂ 4.0) = 549 ÃÂÃÂ 1,847 / 11,135 = 91 kN. F_floor = 458 kN.
Two braced frames in the short direction (18 m): V_per_frame = 549/2 = 274.5 kN.
Brace design:
Brace force at ground level (diagonal brace in 6.0 m bay ÃÂà4.0 m storey height): Brace length = sqrt(6.0ÃÂò + 4.0ÃÂò) = 7.21 m. Angle = tan^(-1)(4.0/6.0) = 33.7ÃÂð.
Horizontal force = 274.5 kN. Brace axial = 274.5 / cos(33.7ÃÂð) = 274.5 / 0.832 = 330 kN (tension or compression).
Try HSS 127ÃÂÃÂ127ÃÂÃÂ8 (350W): A = 3,710 mmÃÂò, r = 48.2 mm. KL/r = 1.0 ÃÂà7,210 / 48.2 = 149.6.
Fe = piÃÂò ÃÂà200,000 / 149.6ÃÂò = 88.2 MPa. lambda = sqrt(350/88.2) = 1.992.
C_r = 0.9 ÃÂÃÂ 3,710 ÃÂÃÂ 350 ÃÂÃÂ (1.0 + 1.992^2.68)^(-0.746) / 1,000 = 0.9 ÃÂÃÂ 3,710 ÃÂÃÂ 350 ÃÂÃÂ 0.314 / 1,000 = 367 kN.
Brace compression = 330 âÃÂä 367 kN. OK. (Ratio = 0.90)
Note: CSA S16 seismic requirements (Clause 27) apply. For MD CBF, KL/r âÃÂä 100 for HSS — HSS 127ÃÂÃÂ127ÃÂÃÂ8 with KL/r = 149.6 does NOT meet MD slenderness limit. Increase to HSS 152ÃÂÃÂ152ÃÂÃÂ10: A = 5,640 mmÃÂò, r = 57.4 mm. KL/r = 7,210/57.4 = 125.6 — still exceeds 100 for MD. Increase to HSS 178ÃÂÃÂ178ÃÂÃÂ10: A = 6,540 mmÃÂò, r = 67.8 mm. KL/r = 7,210/67.8 = 106.3 — close to limit. Use HSS 178ÃÂÃÂ178ÃÂÃÂ13: A = 8,310 mmÃÂò, r = 66.7 mm. KL/r = 7,210/66.7 = 108.1. For LD CBF (R_d = 1.5, R_o = 1.3, KL/r âÃÂä 120): KL/r = 108.1 âÃÂä 120. OK for LD.
Revised seismic — LD CBF:
R_d = 1.5, R_o = 1.3. V = 0.39 ÃÂÃÂ 1.0 ÃÂÃÂ 3,659 / (1.5 ÃÂÃÂ 1.3) = 0.39 ÃÂÃÂ 3,659 / 1.95 = 732 kN. V_per_frame = 366 kN. Brace force = 366 / 0.832 = 440 kN.
C_r = 0.9 ÃÂÃÂ 8,310 ÃÂÃÂ 350 ÃÂÃÂ (1.0 + 1.273^2.68)^(-0.746) / 1,000 = 0.9 ÃÂÃÂ 8,310 ÃÂÃÂ 350 ÃÂÃÂ 0.487 / 1,000 = 1,274 kN.
440 âÃÂä 1,274 kN. OK. (Ratio = 0.35 — capacity governed by analysis, not brace member.)
Column Design — Ground Floor Interior Column
Tributary area: 6.0 m ÃÂà9.0 m = 54 mÃÂò per floor. Two floors + roof.
Axial loads:
| Level | Dead (kN) | Live (kN) |
|---|---|---|
| Roof | (0.30+0.15)ÃÂÃÂ54 = 24.3 | 1.44ÃÂÃÂ54 = 77.8 (snow) |
| Floor | (2.40+0.30+1.00)ÃÂÃÂ54 = 199.8 | 2.17ÃÂÃÂ54 = 117.2 |
| Total | 224.1 | 195.0 |
Factored: C_f = 1.25 ÃÂÃÂ 224.1 + 1.5 ÃÂÃÂ 195.0 = 280.1 + 292.5 = 572.6 kN (snow as companion — check NBCC load combinations. For dead + live dominant: C_f = 1.25 ÃÂÃÂ 224.1 + 1.5 ÃÂÃÂ 117.2 + 0.5 ÃÂÃÂ 77.8 = 280.1 + 175.8 + 38.9 = 494.8 kN.)
Use C_f = 573 kN (snow dominant combination for roof + live for floor — conservative).
Column selection: Ground floor interior, unbraced length = 4.0 m. K = 1.0 (braced frame).
Try W250ÃÂÃÂ58 (350W): A = 7,420 mmÃÂò, r_y = 46.5 mm. KL/r = 4,000/46.5 = 86.0. Fe = piÃÂò ÃÂà200,000 / 86.0ÃÂò = 266.8 MPa. lambda = sqrt(350/266.8) = 1.145. C_r = 0.9 ÃÂà7,420 ÃÂà350 ÃÂà(1.0 + 1.145^2.68)^(-0.746) / 1,000 = 0.9 ÃÂà7,420 ÃÂà350 ÃÂà0.545 / 1,000 = 1,274 kN.
C_f = 573 âÃÂä 1,274 kN. OK. (Ratio = 0.45 — significant reserve for lateral load effects.)
Combined axial + bending from lateral:
Column moment from braced frame action (estimated from analysis): M_f âÃÂà45 kNÃÂ÷m at ground level from frame action.
W250ÃÂÃÂ58: M_rx = 235 kNÃÂ÷m (Class 1). Interaction per Clause 13.8:
C_f/C_r + 0.85 ÃÂàM_f/M_r = 573/1,274 + 0.85 ÃÂà45/235 = 0.450 + 0.163 = 0.613 âÃÂä 1.0. OK.
Drift Check
Lateral drift under factored seismic: estimate from braced frame stiffness.
Frame stiffness (approximate, brace axial deformation dominant): K_frame âÃÂà(A_brace ÃÂàE ÃÂàcosÃÂòtheta) / L_brace for tension brace. K_frame âÃÂà(8,310 ÃÂà200,000 ÃÂà0.692) / 7,210 = 159,000 N/mm = 159 kN/mm.
Drift at roof (from 91 kN): delta_roof = 91/159 = 0.6 mm. Negligible — okay.
Inter-storey drift (from 458 kN at floor): delta_floor = 458/159 = 2.9 mm.
Drift ratio = 2.9/4,000 = 1/1,379 âÃÂä 1/500 per NBCC. OK.
Foundation Interface
Interior column C_f = 573 kN. Use base plate 350 ÃÂÃÂ 350 mm on spread footing.
Concrete bearing: B_r = 0.85 ÃÂÃÂ 0.65 ÃÂÃÂ 25 ÃÂÃÂ 350 ÃÂÃÂ 350 ÃÂÃÂ sqrt(4.0) / 1,000 (limit 2.0) = 0.85 ÃÂÃÂ 0.65 ÃÂÃÂ 25 ÃÂÃÂ 122,500 ÃÂÃÂ 2.0 / 1,000 = 3,384 kN > 573 kN. OK.
Base plate thickness: t_p = 350 ÃÂà0.272 (from previous building design logic) âÃÂàUse 350 ÃÂà350 ÃÂà20 mm base plate.
4-M20 anchor rods, Grade 55, embedded 300 mm into footing. OK for minimum constructability.
Frequently Asked Questions
What is the typical design sequence for a steel building per CSA S16? The design sequence is: (1) establish column grid and framing layout based on architectural requirements; (2) determine dead, live, snow, wind, and seismic loads per NBCC 2020; (3) select the gravity framing system (composite or non-composite beams); (4) select and design the lateral force resisting system (braced frame, moment frame, or shear wall); (5) run structural analysis to determine member forces for all load combinations; (6) size all members for strength (flexure, shear, axial, combined) and serviceability (deflection, vibration, drift); (7) design connections (shear connections, moment connections, brace connections, splices); (8) design foundation interface (base plates, anchor rods). Each step must be verified before proceeding.
How do I choose between a braced frame and a moment frame for the lateral system? Braced frames are more efficient for low-to-mid-rise buildings (up to about 12 storeys) because braces carry axial loads, which is stiffer and more economical than bending in moment frames. Braced frames also have lower drift — typically 40-60% less than moment frames for the same member weight. However, braces obstruct architectural openings (windows, doors, corridors). Moment frames provide clear open bays but require heavier columns and beams, and connection detailing is more expensive. For the example building, a braced frame at the building perimeter (stairwells or exterior walls) is the economical choice.
What live load reduction can I use for Canadian office buildings? Per NBCC 2020 Table 4.1.5.3, live load reduction factor = 0.3 + sqrt(9.8/A) where A is the tributary area in mÃÂò (limited to reduction âÃÂÃÂ¥ 0.5 for most occupancies). For office floors: the reduction applies to beams, girders, and columns. Example: interior column with 54 mÃÂò tributary area per floor, two floors = 108 mÃÂò: reduction = 0.3 + sqrt(9.8/108) = 0.3 + 0.301 = 0.601. Live load on column = 0.601 ÃÂà2.4 = 1.44 kPa (per floor). Snow load is not reduced.
Does the building example include fire protection requirements? The member sizing presented above addresses structural strength and serviceability only — fire protection is a separate design requirement per the National Building Code and CSA S16 Annex K. For a 2-storey office building: (a) columns typically require 1-hour fire resistance rating (spray-applied fireproofing or intumescent coating); (b) floor beams supporting a rated floor assembly require 1-hour protection if the floor is a fire separation; (c) roof members supporting only the roof typically do not require fire protection unless the roof is an occupancy or contains combustible construction. Fire protection thickness is determined by the UL directory based on the W/D ratio (heated perimeter / cross-sectional area) of each section.
Related Pages
- CSA S16 Beam Design
- CSA S16 Column Design
- Canadian Braced Frame Design
- CSA S16 Load Combinations
- Canadian Base Plate Design
- Canadian Framing Systems
- Canadian Seismic Design Guide
- All Canadian References
This page is for educational reference. Complete building design per CSA S16:24 and NBCC 2020. All member sizes, connection details, and foundation designs must be verified by a licensed Professional Engineer for the specific building configuration, site conditions, and local building code requirements. Seismic design parameters must be confirmed from the actual site geotechnical report. Results are PRELIMINARY — NOT FOR CONSTRUCTION without independent PE/SE verification.
Design Resources
Reference pages
Disclaimer: This content is for educational purposes only. Results must be verified by a licensed professional engineer. Steel Calculator provides preliminary design tools — NOT a substitute for professional engineering judgment.