EN 1990 Load Combinations — Partial Factor Combinations per Eurocode
Complete reference for load combinations per EN 1990:2002 Eurocode — Basis of Structural Design. STR/GEO limit state combinations (Equations 6.10, 6.10a/6.10b), partial factors gamma_G and gamma_Q, psi reduction factors for imposed, wind, snow, and temperature actions. Serviceability limit state combinations (characteristic, frequent, quasi-permanent). Worked 3-storey steel office frame load take-down example.
Quick access: European Wind Load | European Snow Load | Seismic Design
EN 1990 Limit States
| Limit State | Symbol | Combination | Checks |
|---|---|---|---|
| Ultimate (STR) | ULS | 6.10 or 6.10a/6.10b | Strength, stability |
| Ultimate (GEO) | ULS | 6.10 or 6.10a/6.10b | Geotechnical failure |
| SLS (characteristic) | SLS | 6.14b | Irreversible damage |
| SLS (frequent) | SLS | 6.15b | Reversible damage |
| SLS (quasi-permanent) | SLS | 6.16b | Long-term effects |
| Accidental | ULS | 6.11a/6.11b | Fire, impact, explosion |
| Seismic | ULS | EN 1998-1 | Earthquake |
ULS Combinations — STR Limit State
Equation 6.10 (Primary)
Sum(gamma_G,j x G_k,j) + gamma_Q,1 x Q_k,1 + Sum(gamma_Q,i x psi_0,i x Q_k,i)
Where:
- gamma_G = 1.35 (unfavourable permanent), 1.00 (favourable permanent)
- gamma_Q = 1.50 (both leading and accompanying variable actions)
Alternative: Equations 6.10a and 6.10b
Some National Annexes (e.g., UK NA) permit using the less onerous of:
| Combination | Permanent (unfavourable) | Leading Variable | Accompanying Variable |
|---|---|---|---|
| 6.10a | 1.35 x G_k | 1.50 x psi_0 x Q_k,1 | 1.50 x psi_0 x Q_k,i |
| 6.10b | xi x 1.35 x G_k | 1.50 x Q_k,1 | 1.50 x psi_0 x Q_k,i |
Where xi = 0.85 (UK NA) or 0.89 (recommended).
PSI Factors for Buildings (EN 1990 Table A1.1)
| Action | psi_0 | psi_1 | psi_2 |
|---|---|---|---|
| Imposed — residential | 0.7 | 0.5 | 0.3 |
| Imposed — offices | 0.7 | 0.5 | 0.3 |
| Imposed — storage | 1.0 | 0.9 | 0.8 |
| Imposed — retail | 0.7 | 0.7 | 0.6 |
| Wind | 0.6 | 0.2 | 0.0 |
| Snow (H <= 1000 m) | 0.5 | 0.2 | 0.0 |
| Snow (H > 1000 m) | 0.7 | 0.5 | 0.2 |
| Temperature (non-fire) | 0.6 | 0.5 | 0.0 |
Worked Example — 3-Storey Steel Office Frame
Location: Manchester, UK. 3 storeys, 6.0 m bay spacing.
| Load Case | Roof (kN/m2) | Floor (kN/m2) |
|---|---|---|
| Self-weight (G_k) | 3.5 | 4.5 |
| Imposed (Q_k) | 0.75 | 3.5 |
| Wind (Q_k) | 0.75 kN/m2 on facade | - |
| Snow (Q_k) | 0.6 | - |
ULS Combination (6.10) — Wind Leading
Roof: 1.35 x 3.5 + 1.50 x 0.75 + 1.50 x 0.7 x 0.75 = 6.65 kN/m2 Floor: 1.35 x 4.5 + 1.50 x 0.7 x 3.5 = 9.76 kN/m2
ULS Combination (6.10) — Imposed Leading
Roof: 1.35 x 3.5 + 1.50 x 0.75 + 1.50 x 0.5 x 0.6 = 6.31 kN/m2 Floor: 1.35 x 4.5 + 1.50 x 3.5 = 11.33 kN/m2
| Location | Governing Load (kN/m2) | Leading Action |
|---|---|---|
| Roof | 6.65 | Wind |
| Floor | 11.33 | Imposed |
National Annex Variations
| Country | Set | gamma_G (unfav) | gamma_Q | xi |
|---|---|---|---|---|
| UK | 6.10a/6.10b | 1.35/1.15 | 1.50 | 0.85 |
| Germany | 6.10 | 1.35 | 1.50 | - |
| France | 6.10 | 1.35 | 1.50 | - |
| Netherlands | 6.10 | 1.35 | 1.50 | - |
| Italy | 6.10 | 1.35 | 1.50 | 0.85 |
Frequently Asked Questions
What is the difference between the 6.10 and 6.10a/6.10b approaches?
Equation 6.10 uses gamma_G = 1.35 for all permanent actions. The 6.10a/6.10b split approach (UK NA, Italian NA) uses two checks: 6.10a with gamma_G = 1.35 and reduced variable action (psi_0 factor on the leading action), and 6.10b with reduced permanent factor (xi x 1.35) and full variable action. The less onerous governs. This can be more economical when permanent actions dominate.
When should wind be the leading variable action vs imposed load?
The leading variable action is whichever produces the most onerous effect. For roof members, wind or snow typically governs. For floor beams, imposed load governs. For global frame stability, wind should be checked as leading. Each ULS combination must be checked with each variable action considered as the leading action.
Related Pages
Educational reference only. Load combinations per EN 1990:2002 Annex A1. Verify psi factors and partial factors against the applicable National Annex. Results are PRELIMINARY - NOT FOR CONSTRUCTION without independent verification.
Design Resources
Calculator tools