Part 1 — Geometry and Modeling (Checks 1-4)

Check 1: Verify grid, story heights, and member orientations

Confirm that the analysis model exactly matches the architectural and structural drawings:

Check 2: Confirm boundary conditions

Boundary conditions determine the global stiffness and force distribution:

Column bases:

Beam ends:

Diaphragm constraints: Rigid diaphragm (all nodes at a floor level have the same lateral displacement) is acceptable if the diaphragm aspect ratio < 3 and openings are < 50% of floor area.

Check 3: Verify material properties and member sizes

Member sizes should match the preliminary design from hand calculations. Check that every member in the model has an assigned section — a member with no section (default section) can produce wildly incorrect stiffness and force distribution results.

Check 4: Verify that the lateral system is complete

Walk through the lateral load path in both directions:

Roof: Wind/seismic force enters the roof diaphragm → diaphragm shear is collected by chords and drag struts → collectors transfer force to vertical LFRS elements (braces or moment frames).

Each floor: Forces accumulate floor by floor. The shear at level i includes forces from levels i through the roof. A brace at the 3rd floor carries the cumulative lateral load from floors 3, 4, 5, and the roof.

Foundation: The vertical LFRS elements transfer overturning forces to the foundation as axial load couples (compression on one column, tension/uplift on the other). The foundation must resist the overturning moment through bearing pressure, pile tension, or dead load weight.

Redundancy check: If one brace or moment frame bay fails, does the building have an alternative load path? For Seismic Design Category D and higher, ASCE 7 requires redundancy factor rho = 1.3 unless sufficient bays exist to provide redundancy.


Part 2 — Load Determination (Checks 5-8)

Check 5: Confirm dead and live loads

Tabulate all dead loads with sources:

Live loads per ASCE 7 Table 4.3-1:

Apply live load reduction (ASCE 7 4.7.2): Lo _ (0.25 + 15/sqrt(KLL _ AT)) >= 0.50 _ Lo for members supporting one floor; >= 0.40 _ Lo for columns supporting multiple floors.

Check 6: Determine wind loads

Per ASCE 7-22 Chapter 27 (directional procedure):

  1. Basic wind speed V per ASCE 7 wind speed map (Risk Category II, 700-year or 1700-year MRI or 300/700/1700 for different risk categories per ASCE 7-22).
  2. Exposure category (B, C, or D) based on terrain roughness.
  3. Topographic factor Kzt (1.0 for flat terrain, > 1.0 for hills/escarpments).
  4. Velocity pressure: qz = 0.00256 _ Kz _ Kzt _ Ke _ V^2 (psf).
  5. External pressure coefficients (GCp) per Fig. 27.3-1 for MWFRS, Fig. 30.3-1 for C&C.
  6. Wind load cases: Case 1 (full wind + torsion), Case 2 (partial wind + torsion), Case 3 (diagonal wind), Case 4 (torsion only).

For a typical office building in Exposure B with V = 115 mph: qh (roof height) ~ 22-28 psf. Total wind base shear ranges from 1-3% of building weight for low-rise buildings to 3-5% for mid-rise.

Check 7: Determine seismic loads

Per ASCE 7-22 Chapter 12 (equivalent lateral force procedure, ELF):

  1. Obtain Ss and S1 from the USGS Seismic Design Maps web application.
  2. Determine site class (A through F) from the geotechnical report.
  3. Compute SMS = Fa _ Ss, SM1 = Fv _ S1; then SDS = 2/3 _ SMS, SD1 = 2/3 _ SM1.
  4. Determine Risk Category (I-IV) and Seismic Design Category (A-F) from Tables 11.6-1 and 11.6-2.
  5. Select lateral system (bearing wall, building frame, moment frame, dual system) and obtain R, Cd, omega_0 from Table 12.2-1.
  6. Approximate period: Ta = Ct * hn^x (Ct = 0.028, x = 0.8 for steel moment frames; Ct = 0.020, x = 0.75 for all others).
  7. Seismic response coefficient: Cs = SDS / (R/Ie), limited to SD1 / (T * R/Ie) for T <= TL.
  8. Base shear: V = Cs _ W, distributed vertically per Fx = Cvx _ V.

For a typical office building in SDC D (SDS = 0.8g, R = 8 for steel SMF): Cs = 0.8 / (8/1.0) = 0.10W. Base shear = 10% of building weight, significantly higher than wind (1-3%). Seismic governs the lateral design in high-seismic regions.

Check 8: Verify load combinations

Ensure all governing combinations are included. The following combos are the most likely to govern:

Comb # LRFD Combination Governing For
LC1 1.4D Foundations, long-span roofs
LC2 1.2D + 1.6L + 0.5Lr Gravity beams, columns
LC3 1.2D + 1.6Lr + 0.5W Roof beams (snow region)
LC4 1.2D + 1.0W + 0.5L + 0.5Lr Lateral drift, wind columns
LC5 0.9D + 1.0W Uplift, net tension in columns
LC6 1.2D + 1.0E + 0.5L + 0.2S Seismic drift, frame members
LC7 0.9D + 1.0E Seismic uplift

Include orthogonal earthquake effects (100% Ex + 30% Ey, then 30% Ex + 100% Ey) per ASCE 7 12.5.3 for columns shared by both orthogonal frames.


Part 3 — Analysis (Checks 9-13)

Check 9: Verify analysis method is appropriate

The analysis method must match the structural configuration per ASCE 7 Table 12.6-1:

For most low-rise and mid-rise buildings: ELF is sufficient. For buildings over 160 ft or with irregular configurations: MRSA is required.

Check 10: Run second-order analysis (P-delta and P-Delta)

Per AISC 360 Ch. C and ASCE 7 12.8.7:

The direct analysis method (DAM) is the preferred approach:

  1. Apply notional loads: Ni = 0.002 * Yi at each floor level in both directions (Yi = total gravity load at level i).
  2. Reduce stiffness: EI* = 0.8 * taub * EI (taub = 1.0 for tau_b * alpha _ Pr/Py <= 0.5; otherwise tau_b = 4 _ (alpha*Pr/Py) * (1 - alpha*Pr/Py)).
  3. Run a second-order (P-delta with large displacement) analysis. The software automatically includes both P-delta (member curvature) and P-Delta (global sidesway) effects.

Stability coefficient check:

theta = Px * delta * Ie / (Vx * hsx * Cd)

Where Px = total vertical load at level x, delta = first-order story drift, Vx = story shear, hsx = story height. If theta > 0.10: P-delta is significant. If theta > 0.25: structure is unstable — redesign required.

Check 11: Verify modal properties (if using MRSA)

Per ASCE 7 12.9.1:

For a 10-story steel moment frame: 15-25 modes are typically needed to capture 90% mass participation due to torsional modes and higher translational modes.

Check 12: Check story drift against code limits

Drift is often the governing design criterion for moment frames:

Wind drift (IBC):

Seismic drift (ASCE 7 12.12):

delta_x = Cd * delta_xe / Ie
delta_x <= allowable = 0.020 * hsx (RC I-II), 0.015 * hsx (RC III), 0.010 * hsx (RC IV)

Where delta_xe is the elastic deflection from the code-prescribed forces (amplified by Cd). For a typical 12 ft story height in SDC D (Cd = 5.5, RC II):

If drift exceeds limits: increase member sizes in the moment frame bay, add bays to the lateral system, or switch to a stiffer system (CBF instead of MRF).

Check 13: Verify torsion and accidental torsion

Per ASCE 7 12.8.4:

For a 150 ft x 100 ft building: Accidental torsion moment Mta = V _ (0.05 _ 150) for load in the 100 ft direction. This adds axial forces to columns on the perimeter, which can be 15-30% of the direct lateral load.

If the inherent torsion is large (amplification factor Ax > 1.0 per ASCE 7 12.8.4.3), the accidental torsion moment must be amplified. Ax = (delta_max / (1.2 * delta_avg))^2 <= 3.0.


Part 4 — Member Design Verification (Checks 14-19)

Check 14: Verify all beams for flexure, shear, and deflection

For every unique beam size and span condition:

Hand-check at least one beam per size. A W21x44 at 28 ft span with composite action should have a D/C ratio of 0.6-0.8 for flexure and 0.4-0.7 for deflection. If your software output shows D/C = 0.95 or 0.15, investigate immediately.

Check 15: Verify all columns for axial + bending interaction

For each column:

Column demand typically peaks at the lowest level (largest accumulated axial load). However, for moment frame columns in taller buildings, the mid-height columns may govern due to higher bending moments from frame action (column hinge formation).

Check 16: Verify all braces for tension and compression

For concentrically braced frames (CBF):

Check 17: Verify collectors, chords, and drag struts

These elements transfer diaphragm forces to the lateral system and are easily overlooked:

Check 18: Verify diaphragm design

The floor/roof diaphragm must transfer lateral forces to the vertical LFRS elements:

Check diaphragm shear: V_diaphragm / b <= V_allow per SDI or AISC Design Guide 16.

Check 19: Verify stability bracing requirements

Per AISC 360 App. 6:


Part 5 — Connection and Foundation (Checks 20-22)

Check 20: Design all typical connections

Prepare connection schedules for:

Each connection schedule must specify: bolt diameter and grade, number of bolts, plate thickness and dimensions, weld size and length, and any special requirements (slip-critical, pretensioned, etc.).

For seismic connections (AISC 341): The connection must develop the expected member strength, not the analysis force. This requires a capacity-based design check where the connection capacity >= 1.1 _ Ry _ Mp (for moment connections) or Ry _ Fy _ Ag (for brace connections).

Check 21: Design column base plates and anchor rods

Base plates for every column on the schedule:

Grout: Specify non-shrink grout under all base plates, minimum 1 in. thickness for leveling. Grout compressive strength >= concrete foundation strength.

Check 22: Coordinate foundation design loads

Extract foundation reactions at every column base:

Organize reactions by foundation type: spread footings, combined footings, pile caps, and mat foundations. The geotechnical engineer needs both the service (ASD) and strength (LRFD) reactions.


Part 6 — Documentation and Review (Checks 23-25)

Check 23: Prepare the structural calculation package

A complete calculation package must include:

  1. Design criteria: Codes (IBC, ASCE 7, AISC 360, AISC 341 if seismic, ACI 318 for foundations), material grades, design assumptions.
  2. Load calculations: Tabulated dead loads, live loads, wind parameters (V, exposure, Kzt, GCp), seismic parameters (Ss, S1, site class, R, Cd, omega_0, SDC).
  3. Analysis model description: Software used, element types, boundary conditions, diaphragm modeling, P-delta settings.
  4. Analysis results: Base shear (wind and seismic, both directions), story drift (all levels, both directions), modal properties (if MRSA), torsion amplification.
  5. Member design: Beam schedule, column schedule, brace schedule — each with D/C ratios for all governing limit states.
  6. Connection design: Connection schedule, standard detail references, special connection calculations.
  7. Foundation reactions: Column base reactions table.
  8. Signed and sealed cover sheet: PE/SE stamp, signature, date.

Check 24: Peer review / senior engineer review

Before submission, have a second engineer review:

Check 25: Final coordination check

Verify that the structural design is coordinated with:


Frame Design Checklist — Quick Reference Card

# Check Code Reference Pass/Fail
1 Grid, story heights, orientations match drawings Structural drawings [ ]
2 Boundary conditions correct (pins, fixes, springs) AISC Ch. C [ ]
3 Material grades and member sizes assigned AISC / ASTM [ ]
4 Lateral system load path complete (roof to foundation) ASCE 7 [ ]
5 Dead + live loads tabulated with sources ASCE 7 Ch. 3-4 [ ]
6 Wind loads per directional procedure ASCE 7 Ch. 27 [ ]
7 Seismic loads per ELF or MRSA ASCE 7 Ch. 11-12 [ ]
8 All governing load combinations included ASCE 7 Ch. 2 [ ]
9 Analysis method appropriate for configuration ASCE 7 12.6 [ ]
10 Second-order (P-delta) analysis run AISC Ch. C / App. 8 [ ]
11 Modal properties verified (90% mass participation) ASCE 7 12.9.1 [ ]
12 Story drift within limits (both directions) ASCE 7 12.12 / IBC [ ]
13 Torsion and accidental torsion included ASCE 7 12.8.4 [ ]
14 All beams verified (flexure, shear, deflection) AISC Ch. F, G [ ]
15 All columns verified (axial + interaction) AISC Ch. E, H [ ]
16 All braces verified (tension + compression) AISC Ch. D, E [ ]
17 Collectors, chords, drag struts designed ASCE 7 12.10 [ ]
18 Diaphragm shear and stiffness checked SDI / AISC DG 16 [ ]
19 Stability bracing requirements met AISC App. 6 [ ]
20 Connection schedule complete AISC Part 10 / DG [ ]
21 Base plates and anchor rods designed AISC J8 / DG 1 [ ]
22 Foundation reactions extracted and coordinated Geotech report [ ]
23 Calculation package complete QA/QC standard [ ]
24 Peer review / senior review complete Office QA/QC [ ]
25 All disciplines coordinated Coordination dwgs [ ]

Related References

Disclaimer

This page is for educational and reference use only. It does not constitute professional engineering advice. All frame designs must be verified against the applicable standard and project specifications by a licensed Professional Engineer (PE) or Structural Engineer (SE). The checklist is a verification aid, not a substitute for engineering judgment.