Thermal Action on Steel — Fire Design & Elevated Temperature

ISO 834 standard fire curve, section factor (Am/V or Hp/A), critical temperature method, steel strength reduction at elevated temperature, fire resistance ratings, and protection methods.

Steel behavior at elevated temperature

Steel does not burn, but it loses strength and stiffness rapidly above 300 degrees C. At 400 degrees C, steel retains approximately 100 percent of its room-temperature yield strength. At 550 degrees C, strength drops to approximately 60 percent. At 700 degrees C, only about 23 percent remains. This is why unprotected steel beams and columns fail within 15-20 minutes in a standard fire — the steel temperature reaches 550-700 degrees C long before the fire is controlled.

The design strategy for steel in fire is to either (a) protect the steel from heat so it stays below a critical temperature during the required fire resistance period, or (b) design the member to carry the fire-condition loads at reduced strength.

Steel strength reduction factors

Temperature (deg C) ky,theta (yield reduction) kE,theta (modulus reduction)
20 1.000 1.000
200 1.000 0.900
300 1.000 0.800
400 1.000 0.700
500 0.780 0.600
550 0.625 0.510
600 0.470 0.310
700 0.230 0.130
800 0.110 0.090

Source: EN 1993-1-2 Table 3.1, AISC Appendix 4 Table A-4.2.1. Values are similar across all codes.

Section factor (Am/V or Hp/A)

The section factor determines how quickly a steel member heats up. It is the ratio of the heated surface area to the volume (mass) of steel. Higher section factors mean faster heating (thinner, lighter members heat faster).

For common cases:

A W14x82 with 4-sided exposure: Am/V = (2 x 10.13 + 2 x 14.31 - 2 x 0.510) / 24.0 = 47.5 / 24.0 = 1.98 in^-1 = 78 m^-1. A W8x31 with 4-sided exposure: Am/V = (2 x 8.00 + 2 x 8.00 - 2 x 0.285) / 9.12 = 31.4 / 9.12 = 3.44 in^-1 = 135 m^-1. The lighter section heats 73 percent faster.

Critical temperature method

The simplest fire design approach determines the temperature at which the member fails under fire-condition loads. Fire loads are reduced from ambient design: the EN 1993-1-2 fire combination is approximately 0.6 to 0.7 times the ambient ULS loads.

The utilization factor in fire: mu_0 = E_fi,d / R_fi,d,0, where E_fi,d = fire-condition design effect, R_fi,d,0 = ambient design resistance.

The critical temperature theta_cr can be read from charts or calculated: theta_cr = 39.19 x ln(1 / (0.9674 x mu_0^3.833) - 1) + 482 (EN 1993-1-2 Eq. 4.22).

For mu_0 = 0.5: theta_cr = 39.19 x ln(1/(0.9674 x 0.5^3.833) - 1) + 482 = 39.19 x ln(1/0.0678 - 1) + 482 = 39.19 x ln(13.75) + 482 = 39.19 x 2.62 + 482 = 585 degrees C.

If the unprotected steel reaches 585 degrees C in 15 minutes but the required fire resistance is 60 minutes, fire protection must slow the heating rate so that 585 degrees C is not reached for at least 60 minutes.

Worked example — fire protection thickness

Member: W14x82 beam, 3-sided exposure (slab above), required fire rating R60 (60 minutes). Critical temperature = 585 degrees C. Section factor Hp/A = 1.55 in^-1 (3-sided) = 61 m^-1.

Using board protection (gypsum, thermal conductivity lambda_p = 0.20 W/mK, density = 800 kg/m^3):

The required protection thickness can be estimated from EN 1993-1-2 Annex D or manufacturer data. For Am/V = 61 m^-1 and theta_cr = 585 degrees C at 60 minutes, typical gypsum board thickness = 15 mm (single layer).

Using intumescent coating: for the same section factor and fire rating, typical dry film thickness = 1.2-1.5 mm. Intumescent coatings expand 20-50 times their thickness when exposed to heat, forming an insulating char layer.

Spray-applied cementitious fireproofing (vermiculite/cement, lambda_p = 0.12 W/mK): required thickness approximately 20-25 mm for R60 at this section factor.

Code comparison — fire design

Aspect AISC App. 4 AS 4100 Sec. 12 EN 1993-1-2 CSA S16 Annex K
Fire curve ASTM E119 (similar to ISO 834) AS 1530.4 (ISO 834) ISO 834 CAN/ULC S101 (ISO 834)
Load combination 1.2D + 0.5L (per IBC) Per AS 1170.0 fire comb. EN 1991-1-2 Eq. 6.11b 1.0D + 0.5L
Critical temp approach App. 4 Section 4.2.4 Cl. 12.5 Cl. 4.2.4 Annex K
Fire ratings Per IBC Table 601 Per NCC Spec C1.1 Per national annex Per NBC Table 3.2.2

All four codes use essentially the same steel property reduction factors and section factor approach. The main differences are in load combinations and how the required fire rating is determined by the building code.

Common pitfalls

Run this calculation

Related references

Disclaimer

This page is for educational and reference use only. It does not constitute professional engineering advice. All design values must be verified against the applicable standard and project specification before use. The site operator disclaims liability for any loss arising from the use of this information.