Thermal Action on Steel — Fire Design & Elevated Temperature
ISO 834 standard fire curve, section factor (Am/V or Hp/A), critical temperature method, steel strength reduction at elevated temperature, fire resistance ratings, and protection methods.
Steel behavior at elevated temperature
Steel does not burn, but it loses strength and stiffness rapidly above 300 degrees C. At 400 degrees C, steel retains approximately 100 percent of its room-temperature yield strength. At 550 degrees C, strength drops to approximately 60 percent. At 700 degrees C, only about 23 percent remains. This is why unprotected steel beams and columns fail within 15-20 minutes in a standard fire — the steel temperature reaches 550-700 degrees C long before the fire is controlled.
The design strategy for steel in fire is to either (a) protect the steel from heat so it stays below a critical temperature during the required fire resistance period, or (b) design the member to carry the fire-condition loads at reduced strength.
Steel strength reduction factors
| Temperature (deg C) | ky,theta (yield reduction) | kE,theta (modulus reduction) | Yield Retention (%) |
|---|---|---|---|
| 20 | 1.000 | 1.000 | 100 |
| 200 | 1.000 | 0.900 | 100 |
| 300 | 1.000 | 0.800 | 100 |
| 400 | 1.000 | 0.700 | 100 |
| 500 | 0.780 | 0.600 | 78 |
| 550 | 0.625 | 0.510 | 63 |
| 600 | 0.470 | 0.310 | 47 |
| 700 | 0.230 | 0.130 | 23 |
| 800 | 0.110 | 0.090 | 11 |
| 900 | 0.060 | 0.068 | 6 |
| 1000 | 0.040 | 0.045 | 4 |
Source: EN 1993-1-2 Table 3.1, AISC Appendix 4 Table A-4.2.1. Values are similar across all codes.
Critical temperature at common utilization ratios
| Utilization Ratio mu_0 | Critical Temperature (deg C) | Meaning |
|---|---|---|
| 0.20 | 730 | Very lightly loaded |
| 0.30 | 680 | Lightly loaded |
| 0.40 | 640 | Moderate loading |
| 0.50 | 585 | Half-capacity utilization |
| 0.60 | 540 | Moderately heavy loading |
| 0.70 | 500 | Heavily loaded |
| 0.80 | 460 | Near full utilization |
| 0.90 | 420 | Very heavily loaded |
Lightly loaded members have higher critical temperatures, meaning they can withstand longer fire exposure before failure. This is why heavy columns often need less fire protection than light beams.
Section factor (Am/V or Hp/A)
The section factor determines how quickly a steel member heats up. It is the ratio of the heated surface area to the volume (mass) of steel. Higher section factors mean faster heating (thinner, lighter members heat faster).
- Am/V — Eurocode notation (m^-1). Am = heated perimeter, V = cross-section area.
- Hp/A — AISC notation (in^-1 or m^-1). Hp = heated perimeter, A = cross-section area.
- ks — AS 4100 notation: ksm = exposed surface area / mass per unit length.
Section factors for common shapes
| Section | Exposure | Am/V (m^-1) | Hp/A (in^-1) | Heating Rate |
|---|---|---|---|---|
| W8x31 | 4-sided | 135 | 3.44 | Fast |
| W12x40 | 4-sided | 104 | 2.65 | Fast |
| W14x82 | 4-sided | 78 | 1.98 | Moderate |
| W14x82 | 3-sided (slab) | 61 | 1.55 | Moderate |
| W21x44 | 4-sided | 97 | 2.47 | Fast |
| W24x55 | 4-sided | 87 | 2.22 | Moderate |
| W24x55 | 3-sided (slab) | 68 | 1.73 | Moderate |
| W27x94 | 4-sided | 65 | 1.65 | Slow |
| W36x150 | 4-sided | 48 | 1.22 | Slow |
| HSS6x6x3/8 | 4-sided | 95 | 2.42 | Fast |
| HSS10x10x1/2 | 4-sided | 58 | 1.47 | Slow |
| HSS12x12x5/8 | 4-sided | 48 | 1.22 | Slow |
Heavy sections (W36x150, HSS12x12x5/8) have low section factors and heat slowly. Light sections (W8x31, W12x40) have high section factors and reach critical temperature in 10-15 minutes unprotected.
Time to reach 550 deg C (unprotected, ISO 834 fire)
| Section Factor (m^-1) | Time to 550 deg C | Time to 700 deg C |
|---|---|---|
| 30 | 35 min | 55 min |
| 50 | 22 min | 35 min |
| 70 | 16 min | 26 min |
| 100 | 12 min | 19 min |
| 150 | 8 min | 14 min |
| 200 | 6 min | 10 min |
| 300 | 4 min | 7 min |
Unprotected steel with Am/V > 100 m^-1 fails within 12 minutes. This is why most building codes require fire protection for structural steel.
Critical temperature method
The simplest fire design approach determines the temperature at which the member fails under fire-condition loads. Fire loads are reduced from ambient design: the EN 1993-1-2 fire combination is approximately 0.6 to 0.7 times the ambient ULS loads.
The utilization factor in fire: mu_0 = E_fi,d / R_fi,d,0, where E_fi,d = fire-condition design effect, R_fi,d,0 = ambient design resistance.
The critical temperature theta_cr can be read from charts or calculated: theta_cr = 39.19 x ln(1 / (0.9674 x mu_0^3.833) - 1) + 482 (EN 1993-1-2 Eq. 4.22).
For mu_0 = 0.5: theta_cr = 39.19 x ln(1/(0.9674 x 0.5^3.833) - 1) + 482 = 39.19 x ln(1/0.0678 - 1) + 482 = 39.19 x ln(13.75) + 482 = 39.19 x 2.62 + 482 = 585 degrees C.
If the unprotected steel reaches 585 degrees C in 15 minutes but the required fire resistance is 60 minutes, fire protection must slow the heating rate so that 585 degrees C is not reached for at least 60 minutes.
Fire protection methods
Spray-applied cementitious (SFRM)
| Parameter | Typical Value | Notes |
|---|---|---|
| Density | 200-400 kg/m^3 | Lightweight to medium |
| Thermal conductivity | 0.08-0.15 W/mK | Varies by product |
| Application thickness | 10-50 mm | Per UL design |
| Application method | Spray (wet mix) | High application rate |
| Surface prep | Clean, primed steel | Primer must be compatible |
| Durability | 30+ years (indoor) | Fragile, not for exposed exterior |
| Fire ratings achieved | R30 to R240 | Most common for buildings |
| Relative cost | 1.0x (baseline) | Cheapest per sqm |
SFRM is the most common fire protection for structural steel in buildings. It is applied by spraying a wet cementitious mix onto primed steel. The resulting coating is relatively fragile and typically concealed behind architectural finishes.
Intumescent paint
| Parameter | Typical Value | Notes |
|---|---|---|
| Dry film thickness | 0.5-5 mm (ambient) | Expands 20-50x in fire |
| Expansion ratio | 20-50x original thickness | Forms insulating char |
| Application | Spray or roller | Requires multiple coats |
| Surface prep | SP 10 / Sa 2.5 minimum | Same as high-performance coating |
| Durability | 25+ years | Aesthetic, can be top-coated |
| Fire ratings achieved | R30 to R120 | Limited by coating thickness |
| Relative cost | 3-5x SFRM | Premium for exposed steel |
Intumescent coatings are used for architecturally exposed structural steel where SFRM would be unsightly. The coating expands when heated to form a thick insulating char layer. Limited to R120 for most products.
Board enclosure
| Parameter | Typical Value | Notes |
|---|---|---|
| Board types | Gypsum, calcium silicate | Factory-produced, consistent |
| Board thickness | 12-50 mm per layer | Multiple layers for higher ratings |
| Installation | Mechanical fixing | Prefabricated, dry trade |
| Surface prep | Minimal | Board encloses the member |
| Durability | 30+ years | Robust, can be decorated |
| Fire ratings achieved | R30 to R240 | Any rating achievable |
| Relative cost | 2-3x SFRM | More expensive but clean finish |
Board enclosures provide a clean, factory-finished appearance. They are preferred where the fire protection must also serve as an architectural finish, or in clean-room and hospital environments where SFRM dust is unacceptable.
Concrete encasement
| Parameter | Typical Value | Notes |
|---|---|---|
| Minimum cover | 40-50 mm | Per code requirements |
| Reinforcement | Light mesh or ties | For crack control |
| Fire ratings achieved | R60 to R240+ | Any rating achievable |
| Relative cost | 4-6x SFRM | Heavy, labor-intensive |
| Weight impact | Significant | Increases foundation loads |
Concrete encasement is the traditional method. It provides excellent fire protection and additional corrosion protection but adds significant weight and cost. Used primarily for columns where concrete fill is also required for structural reasons.
Worked example — fire protection thickness
Member: W14x82 beam, 3-sided exposure (slab above), required fire rating R60 (60 minutes). Critical temperature = 585 degrees C. Section factor Hp/A = 1.55 in^-1 (3-sided) = 61 m^-1.
Using board protection (gypsum, thermal conductivity lambda_p = 0.20 W/mK, density = 800 kg/m^3):
The required protection thickness can be estimated from EN 1993-1-2 Annex D or manufacturer data. For Am/V = 61 m^-1 and theta_cr = 585 degrees C at 60 minutes, typical gypsum board thickness = 15 mm (single layer).
Using intumescent coating: for the same section factor and fire rating, typical dry film thickness = 1.2-1.5 mm. Intumescent coatings expand 20-50 times their thickness when exposed to heat, forming an insulating char layer.
Spray-applied cementitious fireproofing (vermiculite/cement, lambda_p = 0.12 W/mK): required thickness approximately 20-25 mm for R60 at this section factor.
Fire protection thickness by rating and section factor (SFRM)
| Section Factor (m^-1) | R30 (mm) | R60 (mm) | R90 (mm) | R120 (mm) |
|---|---|---|---|---|
| 50 | 10 | 20 | 28 | 35 |
| 100 | 15 | 25 | 35 | 45 |
| 150 | 18 | 30 | 42 | 52 |
| 200 | 20 | 35 | 48 | 60 |
| 300 | 25 | 42 | 58 | 72 |
Approximate thicknesses for cementitious SFRM (density 300 kg/m^3, lambda = 0.12 W/mK). Actual values per manufacturer UL listings.
Code comparison — fire design
| Aspect | AISC App. 4 | AS 4100 Sec. 12 | EN 1993-1-2 | CSA S16 Annex K |
|---|---|---|---|---|
| Fire curve | ASTM E119 (similar to ISO 834) | AS 1530.4 (ISO 834) | ISO 834 | CAN/ULC S101 (ISO 834) |
| Load combination | 1.2D + 0.5L (per IBC) | Per AS 1170.0 fire comb. | EN 1991-1-2 Eq. 6.11b | 1.0D + 0.5L |
| Critical temp approach | App. 4 Section 4.2.4 | Cl. 12.5 | Cl. 4.2.4 | Annex K |
| Fire ratings | Per IBC Table 601 | Per NCC Spec C1.1 | Per national annex | Per NBC Table 3.2.2 |
| Section factor notation | Hp/A (in^-1) | ksm (m^2/tonne) | Am/V (m^-1) | Hp/A (m^-1) |
All four codes use essentially the same steel property reduction factors and section factor approach. The main differences are in load combinations and how the required fire rating is determined by the building code.
Common pitfalls
- Assuming all steel members need the same protection thickness. Heavy columns (low Am/V) heat much slower than light beams (high Am/V). Specifying uniform protection thickness wastes material on heavy members and under-protects light members.
- Ignoring 3-sided vs 4-sided exposure. A beam protected by a concrete slab on its top flange has a significantly lower section factor than the same beam with 4-sided exposure. Using 4-sided values for beams with composite decks over-specifies protection.
- Not checking connection temperatures. Bolts and welds at connections can reach higher temperatures than the mid-span beam if the connection is at a thin web or exposed to fire from multiple sides. EN 1993-1-2 Clause 4.2.1 requires connection checks.
- Specifying intumescent coatings for concealed steelwork. Intumescent coatings must be inspected for correct dry film thickness. If the steel is concealed behind cladding during construction and later, inspection and maintenance are impractical. Board or spray protection is preferred for concealed members.
- Forgetting to account for thermal expansion. A 12 m steel beam heated to 550 deg C expands by approximately 12 x 550 x 12 x 10^-6 = 79 mm. Without expansion joints or sliding connections, this force can damage surrounding construction.
- Using SFRM on architecturally exposed steel. SFRM has a rough, unfinished appearance. For exposed steel, specify intumescent paint or board enclosure that provides a clean architectural finish.
Frequently asked questions
What is the section factor and why does it matter? It is the ratio of heated surface perimeter to cross-section area (Am/V or Hp/A). Higher values mean faster heating. A W8x31 (Am/V = 135 m^-1) reaches critical temperature in 12 minutes unprotected, while a W36x150 (Am/V = 48 m^-1) takes 35 minutes. Section factor determines the required fire protection thickness.
How much does fire protection add to steel cost? SFRM adds approximately 5-10% to structural steel cost. Intumescent paint adds 15-25%. Board enclosure adds 10-15%. Concrete encasement adds 20-30%. The cost depends on required fire rating, section factor, and accessibility.
Do I need to fire-protect steel beams in a parking garage? It depends on the occupancy and local code. Open parking garages (per IBC Section 406.5) may not require fire-rated structural steel if they meet ventilation requirements. Enclosed parking garages typically require 1-hour fire protection per IBC Table 601.
What is the difference between ASTM E119 and ISO 834? They are nearly identical fire curves. Both reach approximately 535 deg C at 5 minutes, 743 deg C at 30 minutes, and 842 deg C at 60 minutes. ISO 834 is used in Europe and Australia. ASTM E119 is used in North America. Design results are interchangeable.
Can I use the critical temperature method for all members? Yes for simple members (beams, columns in axial load or bending). For members with combined loading, complex support conditions, or where the temperature distribution is non-uniform, the advanced calculation method per EN 1993-1-2 Clause 4.3 or finite element analysis may be required.
How does fire protection affect steel connections? Connections must also achieve the required fire rating. Bolt temperatures should not exceed the critical temperature of the connected member. For demand-critical welds in seismic systems, fire protection must cover the entire weld length. Connections at member ends often receive thinner protection due to access, which is a common oversight.
Run this calculation
Related references
- Fire Resistance
- Steel Fire Protection
- Steel Material Properties
- Surface Finish
- Deflection Limits
- Steel Grades
- Column Design
- How to Verify Calculations
Disclaimer
This page is for educational and reference use only. It does not constitute professional engineering advice. All design values must be verified against the applicable standard and project specification before use. The site operator disclaims liability for any loss arising from this information.