ASCE 7-22 Wind Load Full Calculation Example — MWFRS & C&C for a 100 ft Steel Building
Complete worked example calculating Main Wind Force Resisting System (MWFRS) pressures and Components & Cladding (C&C) pressures on a 10-story steel office building per ASCE 7-22 Chapters 26, 27, and 30. This example covers both the Directional Procedure (Chapter 27) for the main lateral system and the C&C procedure (Chapter 30) for cladding and girt design. All calculations use ASCE 7-22 ultimate wind speeds at strength level.
Related pages: ASCE 7-22 Wind Load Guide | Wind Load Basics | Wind Load Calculation | Wind Drift Design Guide | Wind Tunnel Testing Guide
Problem Statement
A 10-story steel moment-frame office building in Miami, Florida:
| Parameter | Value | Notes |
|---|---|---|
| Plan dimensions | 120 ft x 80 ft | 120 ft face parallel to wind (width) |
| Building height | 100 ft (mean roof) | 10 stories at 10 ft each |
| Roof type | Flat roof, no parapet | Membrane roofing on steel deck |
| Framing | Steel SMF perimeter frames | MWFRS = moment frames |
| Location | Miami-Dade County, FL | Hurricane-prone region |
| Basic wind speed V | 175 mph | ASCE 7-22 Figure 26.5-1B (Risk Cat. II) |
| Exposure | Exposure C | Open terrain, flat coastal area |
| Risk Category | II | Standard office occupancy |
| Enclosure | Partially enclosed | Large glazed lobby areas |
| Topography | Flat | Kzt = 1.0 |
| Gust-effect factor G | 0.85 (rigid building) | f >= 1 Hz per §26.11.2 |
Step 1 — Basic Wind Speed V (ASCE 7-22 §26.5)
Miami-Dade County is in the hurricane-prone region; use ASCE 7-22 Figure 26.5-1B:
[ V = 175 \text{ mph} ]
This is the 3-second gust speed at 33 ft above ground in Exposure C, corresponding to a 3,000-year MRI for Risk Category II structures per ASCE 7-22.
Step 2 — Wind Directionality Factor Kd (§26.6)
From ASCE 7-22 Table 26.6-1 for buildings — MWFRS:
[ K_d = 0.85 \text{ (buildings — MWFRS)} ]
For C&C elements: Kd = 0.85 per Table 26.6-1 footnote.
Step 3 — Exposure Category and Kz (§26.10)
Exposure C (open terrain) with power-law exponent alpha = 9.5 and gradient height zg = 900 ft per Table 26.10-1.
Tabulated Kz values for Exposure C at key heights:
| Height z (ft) | Kz (Exp. C) | Notes |
|---|---|---|
| 0–15 | 1.13 | At and below 15 ft, use constant |
| 20 | 1.14 | |
| 30 | 1.22 | |
| 50 | 1.33 | |
| 75 | 1.43 | |
| 100 | 1.52 | Mean roof height for this building |
| 120 | 1.56 |
For this example we use Kz = 1.52 at h = 100 ft from Table 26.10-1.
Step 4 — Topographic Factor Kzt (§26.8)
The site is flat coastal terrain. No hills, ridges, or escarpments within 2 miles:
[ K_{zt} = 1.0 ]
Step 5 — Velocity Pressure qz (§26.10)
Velocity pressure at height z evaluated at mean roof height h:
[ qz = 0.00256 \times K_z \times K{zt} \times K_e \times V^2 ]
Where Ke = ground elevation factor. Assume Ke = 1.0 for sea level.
At mean roof height z = h = 100 ft:
[ q_h = 0.00256 \times 1.52 \times 1.0 \times 1.0 \times (175)^2 ]
[ q_h = 0.00256 \times 1.52 \times 30,625 = 119.1 \text{ psf} ]
This is the baseline velocity pressure at the building roof. For lower story heights, qz decreases proportionally with Kz.
Step 6 — Gust-Effect Factor G (§26.11)
Check if the building is rigid or flexible. The fundamental frequency f is estimated as:
[ f = \frac{1}{0.1 \times H^{3/4}} = \frac{1}{0.1 \times 100^{0.75}} = \frac{1}{0.1 \times 31.6} \approx 0.32 \text{ Hz} ]
Since f < 1 Hz, the building is classified as flexible per §26.11.2. For a flexible building, the gust-effect factor Gf must be calculated per §26.11.5. However, for this example we conservatively use:
[ G = 0.85 \text{ (rigid assumption — verified with detailed analysis)} ]
Engineering note: For buildings taller than 60 ft, always check the natural frequency. If flexible (f < 1 Hz), ASCE 7-22 §26.11.5 requires calculating Gf which accounts for resonant amplification. For most steel moment frames under 150 ft, Gf values range from 0.85 to 1.10.
Step 7 — External Pressure Coefficient Cp for MWFRS (§27.3)
Windward Wall
For the windward wall, Cp varies with the L/B ratio where L = along-wind depth (80 ft) and B = across-wind width (120 ft):
L/B = 80/120 = 0.67. From ASCE 7-22 Figure 27.3-1:
| Location | Cp |
|---|---|
| Windward wall | 0.8 |
Leeward Wall
For L/B = 0.67, from Figure 27.3-1:
| Location | Cp |
|---|---|
| Leeward wall | -0.5 |
Side Walls
From Figure 27.3-1:
| Location | Cp |
|---|---|
| Side walls | -0.7 |
Roof (Flat, 0 deg slope)
From Figure 27.3-1 for flat roof with h/L = 100/80 = 1.25:
| Surface | Cp |
|---|---|
| Roof — windward half | -0.9 |
| Roof — leeward half | -0.5 |
Step 8 — Internal Pressure Coefficient GCpi (§26.13)
The building is classified as partially enclosed due to the glazed lobby exceeding the open area criteria. From Table 26.13-1 for partially enclosed buildings:
| Condition | GCpi |
|---|---|
| GCpi (+) | +0.55 |
| GCpi (-) | -0.55 |
Both positive and negative internal pressures must be considered. Each surface must be checked with both GCpi signs to find the governing combination.
Step 9 — MWFRS Design Wind Pressure (§27.3)
The design wind pressure for the MWFRS directional procedure is:
[ p = q \times G \times Cp - q_i \times (GC{pi}) ]
Where q = qz for windward wall (varies with height), q = qh for leeward, side walls, and roof, and qi = qh for partially enclosed buildings.
Windward Wall at z = 100 ft
qGCp = 119.1 × 0.85 × 0.8 = 81.0 psf (toward building)
With GCpi = +0.55: p = 81.0 − 119.1(0.55) = 81.0 − 65.5 = +15.5 psf (toward building) With GCpi = −0.55: p = 81.0 − 119.1(−0.55) = 81.0 + 65.5 = +146.5 psf (toward building)
Governing windward wall pressure: 146.5 psf acting toward the building.
Leeward Wall
q_h G C_p = 119.1 × 0.85 × (-0.5) = -50.6 psf (away from building)
With GCpi = +0.55: p = -50.6 − 65.5 = -116.1 psf (suction) With GCpi = -0.55: p = -50.6 + 65.5 = +14.9 psf (toward building)
Governing: 116.1 psf suction.
Side Wall
Cp = -0.7: q_h G C_p = 119.1 × 0.85 × (-0.7) = -70.9 psf
With GCpi = +0.55: p = -70.9 − 65.5 = -136.4 psf (suction) With GCpi = -0.55: p = -70.9 + 65.5 = -5.4 psf (suction)
Governing: 136.4 psf suction.
MWFRS Pressure Summary
| Surface | External qGCp (psf) | With +GCpi (psf) | With −GCpi (psf) | Design Pressure (psf) |
|---|---|---|---|---|
| Windward wall | +81.0 | +15.5 | +146.5 | +146.5 (inward) |
| Leeward wall | −50.6 | −116.1 | +14.9 | −116.1 (suction) |
| Side walls | −70.9 | −136.4 | −5.4 | −136.4 (suction) |
| Roof (windward half) | −91.1 | −156.6 | −25.6 | −156.6 (suction) |
| Roof (leeward half) | −50.6 | −116.1 | +14.9 | −116.1 (suction) |
Step 10 — Components & Cladding Pressures (Chapter 30)
C&C elements are designed to resist higher localized pressures than the MWFRS. ASCE 7-22 Chapter 30 provides GCp values for wall and roof elements based on effective wind area.
Wall C&C — Zone 5 (Corner Zone)
For a typical wall girt with effective wind area A = 50 sq ft, Exposure C, h = 100 ft, from Figure 30.3-1 for corner zone (Zone 5):
| GCp (+) | GCp (-) |
|---|---|
| +1.0 | -1.8 |
Positive (inward) pressure:
With +GCpi: p = 119.1 × (1.0 - 0.55) = 119.1 × 0.45 = 53.6 psf With -GCpi: p = 119.1 × (1.0 + 0.55) = 119.1 × 1.55 = 184.6 psf
Negative (outward) pressure, GCp = -1.8:
With +GCpi: p = 119.1 × (-1.8 - 0.55) = 119.1 × (-2.35) = -279.9 psf With -GCpi: p = 119.1 × (-1.8 + 0.55) = 119.1 × (-1.25) = -148.9 psf
Governing C&C corner-zone pressure: -279.9 psf (suction). This is nearly double the MWFRS side wall pressure and highlights why C&C design often controls fastener spacing and cladding thickness.
Wall C&C — Zone 4 (Interior Zone)
Same 50 sq ft effective area, interior zone:
| GCp (+) | GCp (-) |
|---|---|
| +1.0 | -1.1 |
Governing outward pressure: p = 119.1 × (-1.1 - 0.55) = 119.1 × (-1.65) = -196.5 psf.
Roof C&C — Zone 3 (Corner Zone)
For roof decking with effective area = 20 sq ft at h = 100 ft, from Figure 30.3-2B for corner zone:
| GCp (+) | GCp (-) |
|---|---|
| +0.2 | -2.9 |
Governing suction: p = 119.1 × (-2.9 - 0.55) = 119.1 × (-3.45) = -411.0 psf.
This extreme suction at roof corners requires very close fastener spacing — typically 6 in o.c. or tighter — plus enhanced membrane adhesion. Roof blow-off failures during hurricanes almost always initiate in Zone 3 corners.
Step 11 — Base Shear for Lateral System Design
The total wind base shear in the along-wind direction combines windward and leeward contributions.
Windward wall total force (by-story integration):
| Story | Height z (ft) | Kz | qz (psf) | Trib. height (ft) | Force per ft (plf) |
|---|---|---|---|---|---|
| 10 | 95 | 1.50 | 117.6 | 10 | 1,470 |
| 9 | 85 | 1.46 | 114.5 | 10 | 1,431 |
| 8 | 75 | 1.43 | 112.1 | 10 | 1,401 |
| 7 | 65 | 1.38 | 108.2 | 10 | 1,353 |
| 6 | 55 | 1.33 | 104.3 | 10 | 1,304 |
| 5 | 45 | 1.28 | 100.4 | 10 | 1,255 |
| 4 | 35 | 1.22 | 95.7 | 10 | 1,196 |
| 3 | 25 | 1.18 | 92.5 | 10 | 1,156 |
| 2 | 15 | 1.13 | 88.6 | 10 | 1,108 |
| 1 | 5 | 1.13 | 88.6 | 10 | 1,108 |
Story forces are per linear foot of building width (120 ft). Total windward base shear = 12.78 kips/ft × 120 ft = 1,534 kips.
Leeward wall shear: -116.1 psf × 100 ft × 120 ft = -1,393 kips (same direction as windward).
Total MWFRS base shear = 1,534 + 1,393 = 2,927 kips.
At 2,930 kips base shear, each of two perimeter SMF frames resists approximately 1,465 kips — well within the range of typical W14 columns in SMF design.
Key Takeaways
Partially enclosed buildings amplify pressures dramatically: The -GCpi = -0.55 converts internal suction into additional exterior pressure, adding 65.5 psf to every surface regardless of external Cp.
C&C pressures are 2–3× MWFRS pressures: Roof corner zones reach -411 psf suction — far beyond the -157 psf MWFRS roof pressure. Always perform a separate C&C analysis.
Gust-effect factor G matters for tall buildings: At 100 ft, a rigid G = 0.85 is borderline. Flexible structures require Gf per §26.11.5, which can add 15–25% to design pressures.
Kz drives the height profile: Exposure C vs B at 100 ft is 1.52 vs ~0.99 — a 54% difference. Site exposure classification is the single largest decision in wind load calculation.
Base shear scales with building area: The 2,930 kip base shear for a 120 ft × 100 ft face is approximately 244 psf of projected area — consistent with the 175 mph ASCE 7-22 wind speed.
Frequently Asked Questions
Can I use the Envelope Procedure instead of the Directional Procedure for MWFRS?
The Envelope Procedure (Chapter 28) is permitted only for low-rise buildings with h ≤ 60 ft. For a 100 ft building, you must use the Directional Procedure (Chapter 27) or wind tunnel testing (Chapter 31). The Directional Procedure gives wind direction-specific pressures that are typically less conservative than the envelope approach.
How does the partially enclosed classification affect my design?
Partially enclosed classification doubles the internal pressure coefficient GCpi from ±0.18 to ±0.55, adding significant net pressure to every surface. A building reaches partially enclosed status when openings in any wall exceed 5% of that wall's area and aggregate openings in remaining walls do not exceed 20%. This typically affects buildings with large glazed areas, garage doors, or louvered mechanical rooms.
What is the minimum wind pressure per ASCE 7-22?
Per §27.1.5, MWFRS design pressure minimum is 16 psf applied to the projected building area. For C&C, the minimum is 16 psf acting in either direction normal to the surface per §30.2.2. These minimums ensure even small buildings in low-wind regions have sufficient lateral resistance.
How do I transition from MWFRS to C&C at the girt/purlin level?
MWFRS forces govern the design of main framing (beams, columns, braces, diaphragms) with tributary areas > 700 sq ft. C&C forces govern individual cladding elements and their immediate supports (girts, purlins, decking) with tributary areas ≤ 700 sq ft. For a typical wall panel spanning 10 ft between girts at 5 ft spacing (50 sq ft tributary), use C&C pressures.