Wind Loading on Steel Structures — ASCE 7, AS 1170.2, EN 1991-1-4

Wind load determination: velocity pressure (qz), exposure categories, MWFRS vs C&C pressures, directional procedure, and cross-code comparison.

Wind load fundamentals

Wind load on a building is the result of air flowing around and over the structure, creating positive pressure on the windward face, negative pressure (suction) on the leeward and side faces, and uplift on the roof. The magnitude depends on wind speed, terrain exposure, building height, shape, and the tributary area of the component being designed.

Wind loading governs the lateral design of most low-rise and mid-rise steel buildings in non-seismic regions. It also governs the design of roof cladding, purlins, girts, and connections in virtually all buildings regardless of seismic zone.

ASCE 7-22 velocity pressure formula

The fundamental equation for velocity pressure at height z is:

qz = 0.00256 x Kz x Kzt x Kd x Ke x V^2 (psf)

where:

Exposure categories

Category Description Example Kz at 33 ft Kz at 100 ft
B Urban, suburban, wooded City center, dense residential 0.70 0.90
C Open terrain, scattered obstructions Flat farmland, airport 0.85 1.04
D Flat, unobstructed waterfront Coastal, lake shore 0.99 1.16

Exposure B produces the lowest wind loads; Exposure D the highest. Most building sites default to Exposure C unless the engineer can demonstrate that sufficient upwind roughness exists for Exposure B (requires 2,600 ft of roughness in all directions for MWFRS).

MWFRS vs C&C

ASCE 7 distinguishes between:

This distinction means a purlin designed for MWFRS pressures is under-designed. Always use C&C pressures for individual framing members.

Worked example — MWFRS wind pressure on a 3-story building

Building: 3-story office, 40 ft (12.2 m) tall, 100 ft x 60 ft plan, flat roof. Location: V = 115 mph (ASCE 7-22, Risk Category II). Exposure C. Flat terrain (Kzt = 1.0). Sea level (Ke = 1.0). Kd = 0.85.

Velocity pressure at roof height (z = 40 ft): Kz = 0.87 (from ASCE 7 Table 26.10-1, Exposure C, interpolated). qz = 0.00256 x 0.87 x 1.0 x 0.85 x 1.0 x 115^2 = 0.00256 x 0.87 x 0.85 x 13,225 = 25.0 psf.

Design wind pressure on windward wall (MWFRS, Directional Procedure): p = q x G x Cp - qi x (GCpi). For windward wall: Cp = 0.8, G = 0.85 (rigid building gust factor). p_windward = 25.0 x 0.85 x 0.8 = 17.0 psf (external). For leeward wall (L/B = 100/60 = 1.67): Cp = -0.35. p_leeward = 25.0 x 0.85 x (-0.35) = -7.4 psf (suction).

Total frame pressure at roof level = 17.0 - (-7.4) = 24.4 psf (net, windward to leeward). For a 3-story braced frame, base shear is approximately: V = average pressure x tributary height x building width = 22 psf (averaged over height) x 40 ft x 60 ft = 52,800 lb = 52.8 kips.

Internal pressure: For an enclosed building, GCpi = +/- 0.18. Internal pressure = 0.18 x 25.0 = 4.5 psf. This adds to or subtracts from the external pressure on each surface.

Code comparison — wind load provisions

Aspect ASCE 7-22 AS/NZS 1170.2 EN 1991-1-4 NBCC 2020
Reference wind speed 3-second gust at 33 ft 3-second gust at 10 m (regional) 10-min mean at 10 m Hourly mean at 10 m
Speed conversion V_3s (direct) V_R (regional) V_b x c_dir x c_season q = CV^2 (tables)
Pressure formula qz = 0.00256 Kz Kzt Kd Ke V^2 qz = 0.5 x rho x [V_des x M_z,cat]^2 qp(z) = 0.5 x rho x v_m^2(z) x [1 + 7Iv(z)] p = Iw x q x Ce x Ct x Cp
Exposure categories B, C, D Terrain categories 1-4 Terrain categories 0-IV Open, rough
Internal pressure GCpi = +/- 0.18 (enclosed) Cpi (Table 5.1) cpi (Table 7.1) Cpi (Table)
C&C method Chapter 30 Cl. 5.4 (local pressure) EN 1991-1-4 Cl. 7.2 NBCC Commentary

The wind speed definitions differ significantly between codes. ASCE 7 uses a 3-second gust, EN 1991-1-4 uses a 10-minute mean, and NBCC uses an hourly mean. A 3-second gust of 115 mph corresponds to approximately an hourly mean of 80 mph. Converting between codes requires careful attention to the gust factor and averaging period.

Common pitfalls

ASCE 7-22 Chapters 26-30 procedure overview

ASCE 7-22 organizes wind load provisions into six chapters, each addressing a different building type or calculation method. Understanding which chapter applies is the first step in any wind design:

Chapter Title Building type Method
26 General Requirements All buildings Definitions, wind speed maps, exposure categories, Kz/Kzt/Kd tables
27 MWFRS - Directional Procedure Enclosed, partially enclosed, and open buildings of all heights Calculate pressures on each surface using Cp and GCpf coefficients
28 MWFRS - Envelope Procedure Enclosed and partially enclosed low-rise buildings (h <= 60 ft) Two-way loading using GCpf coefficients from Figure 28.3-1
29 MWFRS - Buildings with Gable/Mansard Roofs Specific roof geometries Pressure coefficients for various roof angles and geometries
30 Components and Cladding All buildings C&C pressure coefficients for walls, roofs, and openings

Step-by-step wind load determination per ASCE 7-22

  1. Determine Risk Category (I, II, III, or IV) from ASCE 7 Table 1.5-1 based on building occupancy
  2. Obtain basic wind speed V from ASCE 7 Figures 26.5-1A through 26.5-1D based on Risk Category and location
  3. Determine wind directionality factor Kd from ASCE 7 Table 26.6-1 (0.85 for buildings)
  4. Determine exposure category (B, C, or D) from ASCE 7 Section 26.7
  5. Determine topographic factor Kzt from ASCE 7 Section 26.8 (1.0 for flat terrain)
  6. Determine ground elevation factor Ke from ASCE 7 Table 26.9-1 (1.0 at sea level)
  7. Calculate velocity pressure qz using ASCE 7 Eq. 26.10-1
  8. Determine external pressure coefficients (Cp for MWFRS, GCp for C&C)
  9. Determine internal pressure coefficient GCpi from ASCE 7 Table 26.13-1
  10. Calculate design wind pressure p = qz x G x Cp - qi x GCpi (MWFRS) or p = qz x GCp - qi x GCpi (C&C)

Velocity pressure coefficients Kz table

The velocity pressure exposure coefficient Kz varies by exposure category and height above ground. These are the most frequently referenced values in wind load calculations:

Height z (ft) Exposure B Exposure C Exposure D
0-15 0.57 0.85 0.98
20 0.62 0.90 1.02
25 0.66 0.94 1.06
30 0.70 0.98 1.09
40 0.76 1.04 1.14
50 0.81 1.09 1.18
60 0.85 1.13 1.22
80 0.91 1.20 1.28
100 0.96 1.25 1.33
120 1.01 1.30 1.37
160 1.09 1.38 1.44
200 1.15 1.44 1.50
300 1.26 1.55 1.60
400 1.34 1.63 1.67
500 1.41 1.70 1.73

Interpolation between values is permitted. These coefficients are derived from power-law wind profiles: Kz = 2.01 x (z/zg)^(2/alpha), where zg and alpha depend on exposure category.

Topographic factor Kzt

For buildings on hills, ridges, or escarpments, Kzt > 1.0 increases the design wind speed. The calculation uses ASCE 7 Figure 26.8-1:

Kzt = (1 + K1*K2*K3)^2
Parameter Definition Range
K1 Factor accounting for shape of topographic feature (hill, escarpment, ridge) 0.0 to 0.8
K2 Factor accounting for reduction in speed-up with distance upwind/downwind of crest 0.0 to 1.0
K3 Factor accounting for reduction in speed-up with height above ground 0.0 to 1.0

Typical values: flat terrain Kzt = 1.0; building on a 200 ft hill with 1:3 slope Kzt = 1.3-1.6; coastal escarpment Kzt = 1.2-1.5. Engineers should check Kzt whenever the building site is within 10 times the hill height of a significant topographic feature.

Wind directionality factor Kd

Structure type Kd
Buildings (all) 0.85
Chimneys, tanks, rooftop equipment 0.90
Solid freestanding walls and signs 0.85
Open signs, lattice frameworks, trussed towers 0.85
Arched roofs 0.85

The factor 0.85 accounts for the reduced probability that the maximum wind speed will occur simultaneously from the least favorable direction. It should not be applied when checking specific directions (e.g., a building with a large opening facing a dominant wind direction).

Velocity pressure calculation example (detailed)

Given: 10-story office building, 130 ft tall, 120 ft x 80 ft plan, flat roof. Located in Dallas, TX. Risk Category II. Exposure C. Flat terrain.

Step 1 - Basic wind speed: From ASCE 7-22 Figure 26.5-1A, V = 115 mph (Risk Category II, 700-year MRI).

Step 2 - Velocity pressure at roof height (z = 130 ft):

q130 = 0.00256 x 1.32 x 1.0 x 0.85 x 1.0 x 115^2
     = 0.00256 x 1.32 x 0.85 x 13,225
     = 0.00287 x 13,225
     = 37.9 psf

Step 3 - Velocity pressure at mid-height (z = 65 ft):

q65 = 0.00256 x 1.15 x 1.0 x 0.85 x 1.0 x 115^2 = 33.1 psf

Step 4 - Velocity pressure at 30 ft:

q30 = 0.00256 x 0.98 x 1.0 x 0.85 x 1.0 x 115^2 = 28.2 psf

Step 5 - Gust factor G: For a rigid building (T < 1.0 sec), G = 0.85 (ASCE 7 Table 26.11-1). Building period T approximately 0.1N = 1.0 sec. Since T is close to 1.0 sec, verify that the building is rigid. If T > 1.0 sec, use the flexible building gust factor procedure.

MWFRS vs C&C: detailed comparison

Parameter MWFRS (Chapter 27/28) C&C (Chapter 30)
Purpose Design the lateral force-resisting system (braces, moment frames, shear walls, diaphragms) Design individual cladding elements, purlins, girts, fasteners
Tributary area Large (entire building face, full story height) Small (individual panel or framing member)
Pressure coefficients Lower (averaged over large area) Higher (local peak pressures at corners, edges)
Gust factor G = 0.85 (rigid) or calculated (flexible) Built into GCp values
Critical locations Overall building overturning, base shear, story drift Roof corners, roof edges, wall corners near roof
Typical pressure ratio 1.0 (baseline) 1.5 to 3.5 times MWFRS values at critical zones

C&C roof pressure zones

ASCE 7-22 Chapter 30 defines distinct roof pressure zones with dramatically different pressures:

Zone Location GCp (typical, h <= 60 ft) Relative pressure
Zone 1 Interior roof area (away from edges) -0.9 to -1.1 Baseline
Zone 2 Roof edge (strip along perimeter) -1.3 to -1.7 1.3-1.5x Zone 1
Zone 3 Roof corner (triangular area at corners) -2.0 to -2.6 2.0-2.5x Zone 1

The Zone 3 corner suction can be 2-3 times the Zone 1 interior pressure. This is why roof failures in hurricanes typically begin at corners - the local peak suction exceeds the fastener capacity even when the interior roof is adequate.

Positive and negative pressure zones on buildings

Wind creates both positive (inward) and negative (outward/suction) pressures on different building surfaces:

Surface Pressure direction Cp value (MWFRS, rectangular building) Notes
Windward wall Positive (inward) +0.60 to +0.80 Increases with L/B ratio
Leeward wall Negative (suction) -0.20 to -0.50 Depends on L/B ratio
Side walls Negative (suction) -0.60 to -0.70 Approximately uniform
Flat roof (windward edge) Negative (suction) -0.90 to -1.30 Highest near windward edge
Flat roof (center) Negative (suction) -0.50 to -0.70 Lower than edges
Flat roof (leeward) Negative (suction) -0.30 to -0.50 Lowest magnitude

The net lateral force on the building is the algebraic sum of windward positive and leeward negative pressures. For a typical rectangular building with L/B = 2, the net Cp = 0.80 - (-0.30) = 1.10.

Parapet and roof corner loads

Parapets and roof corners experience the highest wind pressures on a building and require special attention:

Parapet pressure (ASCE 7-22 Section 30.9)

Parapets are loaded on both the windward and leeward faces simultaneously. The net pressure is the sum of positive pressure on the windward face and suction on the leeward face:

p_parapet = q_p x (GCpn)
Parapet zone GCpn (net) Typical pressure (115 mph, Exposure C, 40 ft)
Windward parapet (corner zone) +1.8 / -2.2 48 to 59 psf
Windward parapet (interior zone) +1.3 / -1.6 35 to 43 psf

Roof corner loads

At roof corners, the interaction of windward wall separation and roof edge vortex creates extreme suction. For C&C design:

Roof zone Area (ft2) GCp Pressure (psf, 115 mph, 40 ft)
Corner Zone 3 (10 ft x 10 ft) 10 -2.6 -70 psf uplift
Corner Zone 3 (100 ft2) 100 -1.9 -51 psf uplift
Corner Zone 3 (500 ft2) 500 -1.4 -38 psf uplift

These pressures explain why mechanically attached roof membranes in hurricane zones require enhanced fastening patterns at corners and edges.

Simplified vs analytical method comparison

ASCE 7-22 offers simplified procedures for common building types and analytical procedures for complex conditions:

Feature Simplified (Chapter 27 Part 2) Analytical (Chapter 27 Part 1)
Building height limit h <= 160 ft No limit
Building shape Regular (rectangular) Any shape
Roof type Flat, gable, hip, mansard (limited) All roof types
Exposure C or D (Exposure B not permitted) B, C, or D
Topography Flat only (Kzt = 1.0) Any topography
Flexibility Rigid buildings only (T < 1.0 sec) Rigid and flexible
Pressure determination Direct from tables (p_s30, p_net) Calculate using Cp, GCp, G
Ease of use Simple look-up Requires multi-step calculation
Accuracy Conservative (10-20% higher) More precise
Best for Preliminary design, simple buildings Final design, complex buildings

For most structural steel buildings, the analytical method (Chapter 27 Part 1) is preferred because it provides more accurate and often lower design pressures, and it accommodates the full range of building geometries encountered in practice.

Run this calculation

Related references

Disclaimer

This page is for educational and reference use only. It does not constitute professional engineering advice. All design values must be verified against the applicable standard and project specification before use. The site operator disclaims liability for any loss arising from the use of this information. [object Object]

[object Object]

Frequently Asked Questions

What is the recommended design procedure for this structural element?

The standard design procedure follows: (1) establish design criteria including applicable code, material grade, and loading; (2) determine loads and applicable load combinations; (3) analyze the structure for internal forces; (4) check member strength for all applicable limit states; (5) verify serviceability requirements; and (6) detail connections. Computer analysis is recommended for complex structures, but hand calculations should be used for verification of critical elements.

How do different design codes compare for this calculation?

AISC 360 (US), EN 1993 (Eurocode), AS 4100 (Australia), and CSA S16 (Canada) follow similar limit states design philosophy but differ in specific resistance factors, slenderness limits, and partial safety factors. Generally, EN 1993 uses partial factors on both load and resistance sides (γM0 = 1.0, γM1 = 1.0, γM2 = 1.25), while AISC 360 uses a single resistance factor (φ). Engineers should verify which code is adopted in their jurisdiction.

Design Resources

Calculator tools

Design guides