-- | ----- | -------------------------------------------------------------------- | | a0 | 0.13 | Hot-finished hollow sections (CHS, RHS), S460 up to 40 mm | | a | 0.21 | UC and UB about y-y axis (tf <= 40 mm), hot-finished RHS S355 | | b | 0.34 | UC and UB about z-z axis (tf <= 40 mm) -- most common UK column case | | c | 0.49 | UC and UB z-z (tf > 40 mm), channels, angles, cold-formed RHS | | d | 0.76 | Cold-formed RHS S420-S460, welded box sections with tf > 40 mm |
The selection depends on the cross-section type, the axis of buckling, the steel grade, the flange thickness, and the manufacturing process (hot-rolled vs cold-formed vs welded). Table 6.2 provides the definitive mapping.
Buckling Curve for UK Sections
| Section Type | Buckling Axis | tf <= 40 mm | 40 < tf <= 100 mm |
|---|---|---|---|
| UC (Universal Column) | y-y (major) | a (alpha=0.21) | a (alpha=0.21) |
| UC (Universal Column) | z-z (minor) | b (alpha=0.34) | c (alpha=0.49) |
| UB (Universal Beam) | y-y (major) | a (alpha=0.21) | a (alpha=0.21) |
| UB (Universal Beam) | z-z (minor) | b (alpha=0.34) | c (alpha=0.49) |
| CHS (hot-finished) | any | a (alpha=0.21) | a (alpha=0.21) |
| RHS (hot-finished) | any, S235-S355 | a (alpha=0.21) | a (alpha=0.21) |
| RHS (cold-formed) | any, S235-S355 | c (alpha=0.49) | c (alpha=0.49) |
| Angle, Channel | any | c (alpha=0.49) | c (alpha=0.49) |
| Welded box | any | b/c | c/d |
For the vast majority of UK building columns (UC sections, S275 or S355, tf <= 40 mm), buckling about the z-z (weak) axis with curve b (alpha = 0.34) governs.
Lambda_1 Values for UK Steel Grades
| Grade | fy (MPa) | epsilon = sqrt(235/fy) | lambda_1 = 93.9 x epsilon |
|---|---|---|---|
| S235 | 235 | 1.000 | 93.9 |
| S275 | 275 | 0.924 | 86.8 |
| S355 | 355 | 0.814 | 76.4 |
| S460 | 460 | 0.715 | 67.1 |
For S355, lambda_1 = 76.4, meaning that a column with slenderness ratio Lcr/i = 76.4 has lambda_bar = 1.0 -- the point at which buckling and yielding effects are equal. Below this, yielding dominates; above, buckling dominates.
Tabulated Chi Values
| lambda_bar | chi (a0) alpha=0.13 | chi (a) alpha=0.21 | chi (b) alpha=0.34 | chi (c) alpha=0.49 | chi (d) alpha=0.76 |
|---|---|---|---|---|---|
| 0.2 | 1.000 | 1.000 | 1.000 | 1.000 | 1.000 |
| 0.3 | 0.991 | 0.979 | 0.959 | 0.929 | 0.874 |
| 0.4 | 0.977 | 0.953 | 0.917 | 0.871 | 0.797 |
| 0.5 | 0.956 | 0.920 | 0.871 | 0.813 | 0.726 |
| 0.6 | 0.926 | 0.877 | 0.817 | 0.751 | 0.657 |
| 0.7 | 0.886 | 0.826 | 0.758 | 0.687 | 0.593 |
| 0.8 | 0.837 | 0.770 | 0.696 | 0.624 | 0.533 |
| 0.9 | 0.782 | 0.711 | 0.636 | 0.565 | 0.478 |
| 1.0 | 0.724 | 0.652 | 0.578 | 0.511 | 0.429 |
| 1.2 | 0.612 | 0.543 | 0.474 | 0.414 | 0.344 |
| 1.4 | 0.509 | 0.446 | 0.386 | 0.335 | 0.276 |
| 1.6 | 0.420 | 0.366 | 0.315 | 0.272 | 0.223 |
| 1.8 | 0.348 | 0.302 | 0.259 | 0.223 | 0.182 |
| 2.0 | 0.291 | 0.251 | 0.215 | 0.185 | 0.150 |
Worked Example -- 254UC in S355
Given:
- Section: 254 x 254 x 89 UC, S355J2
- L = 4.0 m, pinned ends, braced frame: Lcr,y = Lcr,z = 4.0 m
- N_Ed = 1,800 kN
Section properties (from SCI Blue Book): h = 260.4 mm, b = 256.3 mm, tw = 10.5 mm, tf = 17.3 mm A = 114 cm^2 = 11,400 mm^2 i_y = 11.4 cm = 114 mm, i_z = 6.59 cm = 65.9 mm tf = 17.3 mm <= 40 mm, so curve a for y-y, curve b for z-z.
Slenderness: lambda_1 = 93.9 x sqrt(235/355) = 76.4 lambda_bar_y = (4,000 / 114) / 76.4 = 35.1 / 76.4 = 0.459 lambda_bar_z = (4,000 / 65.9) / 76.4 = 60.7 / 76.4 = 0.794
Reduction factors: y-y, curve a (alpha = 0.21): Phi_y = 0.5 x [1 + 0.21 x (0.459 - 0.2) + 0.459^2] = 0.5 x [1 + 0.054 + 0.211] = 0.633 chi_y = 1 / [0.633 + sqrt(0.633^2 - 0.459^2)] = 1 / [0.633 + 0.435] = 0.936
z-z, curve b (alpha = 0.34): Phi_z = 0.5 x [1 + 0.34 x (0.794 - 0.2) + 0.794^2] = 0.5 x [1 + 0.202 + 0.630] = 0.916 chi_z = 1 / [0.916 + sqrt(0.916^2 - 0.794^2)] = 1 / [0.916 + 0.456] = 0.729
Buckling resistance: N_b,Rd,y = 0.936 x 11,400 x 355 / 1.0 = 3,788 kN N_b,Rd,z = 0.729 x 11,400 x 355 / 1.0 = 2,950 kN (governs)
Utilisation: N_Ed / N_b,Rd,z = 1,800 / 2,950 = 0.61. OK.
Worked Example -- UB Section Used as Column
Given:
- Section: 356 x 171 x 51 UB, S355
- L = 3.5 m, pinned ends
- N_Ed = 850 kN
This UB section is being used as a lightly loaded column, perhaps in a low-rise frame. Note that UB sections used as columns are more efficient about the y-y axis but the z-z axis buckling is more critical.
Section properties: h = 355.0 mm, b = 171.5 mm, tw = 7.3 mm, tf = 11.5 mm A = 64.9 cm^2 = 6,490 mm^2 i_y = 14.7 cm = 147 mm, i_z = 3.93 cm = 39.3 mm tf = 11.5 mm <= 40 mm.
Slenderness: lambda_bar_y = (3,500 / 147) / 76.4 = 23.8 / 76.4 = 0.312 lambda_bar_z = (3,500 / 39.3) / 76.4 = 89.1 / 76.4 = 1.166
The weak-axis slenderness of 1.166 means the column is firmly in the buckling range.
Reduction factor z-z (curve b): Phi_z = 0.5 x [1 + 0.34 x (1.166 - 0.2) + 1.166^2] = 0.5 x [1 + 0.328 + 1.360] = 1.344 chi_z = 1 / [1.344 + sqrt(1.344^2 - 1.166^2)] = 1 / [1.344 + 0.667] = 0.497
Buckling resistance: N_b,Rd,z = 0.497 x 6,490 x 355 / 1.0 = 1,145 kN > 850 kN. OK at 74% utilisation.
This is a typical efficiency for UB columns: chi_z approximately 0.5 at moderate slenderness.
UK National Annex Provisions
The UK NA to BS EN 1993-1-1 confirms:
- gamma_M1 = 1.00 for buckling resistance of members, unchanged from the recommended value.
- The buckling curves a0-d and their associated imperfection factors are adopted without modification.
- For S460 steel, the UK NA confirms that the curve selection for hot-rolled sections is the same as for S235-S355, with curve a0 applicable only to hot-finished hollow sections.
- For flexural-torsional buckling (Clause 6.3.1.4), the UK NA adopts the recommended provisions without change, noting that single-symmetric sections (channels, tees) require explicit consideration of the interaction between flexural and torsional buckling modes.
Design Resources
- UK Steel Grades Reference -- EN 10025-2 grade selection
- UK Steel Properties -- fy, fu tables
- UK UC and UB Section Properties -- Dimensions and section properties
- UK Effective Length Factors -- Annex E k factors
- UK Combined Loading Design -- Beam-column interaction
- All UK Steel Design References -- complete library
Try Our Free Calculator
Check your UK column buckling calculations with our free UK Column Capacity Calculator — full derivation, code clause references, instant results.
Open UK Column Capacity Calculator âÃÂÃÂ
Frequently Asked Questions
Which buckling curve applies to a UK UC column?
For a Universal Column (UC) in a UK building, with tf <= 40 mm: buckling about the y-y (major) axis uses curve a (alpha = 0.21), and buckling about the z-z (minor) axis uses curve b (alpha = 0.34). Since columns typically buckle about the weaker z-z axis, curve b is the most common for UK UC sections. For heavy UC sections with tf > 40 mm, the z-z axis curve upgrades to c (alpha = 0.49).
How do I calculate the non-dimensional slenderness lambda_bar?
lambda_bar = (Lcr / i) / lambda_1, where lambda_1 = 93.9 x sqrt(235/fy). For S355: lambda_1 = 76.4. For S275: lambda_1 = 86.8. The effective length Lcr = k x L, where k is the effective length factor from EN 1993-1-1 Annex E. For a braced frame column with simple connections: k = 1.0, giving Lcr = L.
What effective length should I use for a braced frame column?
For a braced frame column with nominally pinned connections, Lcr = 1.0 x L (storey height). This is the standard assumption for UK simple construction. With partial rotational restraint (e.g., flush end plate connections), k may reduce to 0.85-1.0 per Annex E. The UK NA confirms that simple connections (fin plates, partial-depth end plates) do not provide significant rotational restraint, supporting the conservative use of k = 1.0.
At what lambda_bar does a column transition from cross-section yielding to buckling?
The transition region is lambda_bar = 0.2 to 0.4. Below 0.2, chi >= 0.98 and buckling effects are negligible -- the column can be designed for cross-section resistance only (N_Ed <= N_pl,Rd). Above 0.4, chi drops significantly and buckling governs. At lambda_bar = 1.0 (the Euler reference slenderness), chi = 0.58 for curve b -- the column achieves 58% of its squash load. At lambda_bar = 2.0, chi = 0.22 -- only 22% of the squash load is available, and a more efficient section should be selected.
Educational reference only. All design values are per BS EN 1993-1-1:2005 + UK National Annex and BS EN 10025-2:2019. Verify all values against the current editions of the standards and the applicable National Annex for your project jurisdiction. Designs must be independently verified by a Chartered Structural Engineer registered with the Institution of Structural Engineers (IStructE) or the Institution of Civil Engineers (ICE). Results are PRELIMINARY -- NOT FOR CONSTRUCTION without independent professional verification.