CSA S16 Beam Design — Worked Example
Quick Reference: This worked example designs a W610x125 beam in Grade 350W for a 8 m simple span under NBCC 2020 factored loads. Checks include flexure (Cl. 13.5/13.6), shear (Cl. 13.4), deflection (L/360 live load), and lateral bracing requirements (Cl. 13.6.5).
Comprehensive worked examples are essential for understanding CSA S16 beam design. This guide takes you through a complete beam design from loads to final section selection, with all intermediate calculations shown.
Design Problem
Given:
- Beam span: 8.0 m (simple supports)
- Tributary width: 4.0 m (beams at 4 m spacing)
- Dead load: 3.0 kPa (50 mm concrete slab on steel deck + mechanical + ceiling)
- Live load: 4.0 kPa (open office per NBCC Table 4.1.5.3)
- Steel grade: CSA G40.21 350W
- Lateral bracing: Full bracing at supports, intermediate braces at 2.67 m spacing (third points)
- Simply supported beam with uniform distributed loads
- Deflection limit: L/360 for live load
Objective: Select an adequate W-shape beam and verify all limit states.
Step 1 — Factored Loads Per NBCC 2020
Unfactored loads:
Dead load: w_D = 3.0 kPa × 4.0 m = 12.0 kN/m Self-weight: Estimate W610x125 → 1.25 kN/m (W610x125 = 125 kg/m × 9.81 m/s² / 1,000) Total dead: w_D = 12.0 + 1.25 = 13.25 kN/m
Live load: w_L = 4.0 kPa × 4.0 m = 16.0 kN/m
Factored load (ULS):
Governing combination: NBCC Comb. 2 — 1.25D + 1.5L
w_f = 1.25 × 13.25 + 1.5 × 16.0 = 16.56 + 24.0 = 40.56 kN/m
Maximum factored moment:
M_f = w_f × L² / 8 = 40.56 × 8.0² / 8 = 40.56 × 64 / 8 = 324.5 kN·m
Maximum factored shear:
V_f = w_f × L / 2 = 40.56 × 8.0 / 2 = 162.2 kN
Step 2 — Select Trial Section
Required plastic modulus (assuming Class 1 or 2 section):
Z_x_req = M_f / (φ × F_y) = 324.5 × 10⁶ / (0.90 × 350) = 1.030 × 10⁶ mm³
Try W610x125 (US equivalent W24x84):
| Property | Value |
|---|---|
| d | 612 mm |
| b_f | 229 mm |
| t_f | 19.6 mm |
| t_w | 11.9 mm |
| Z_x | 3,330 × 10³ mm³ |
| S_x | 2,970 × 10³ mm³ |
| I_x | 908 × 10⁶ mm⁴ |
| r_y | 49.8 mm |
| Mass | 125 kg/m → 1.23 kN/m |
Actual self-weight = 1.23 kN/m vs estimated 1.25 kN/m — close enough. No iteration needed.
Step 3 — Section Classification (Cl. 11.2, Table 2)
Flange classification (for flexure):
b = b_f / 2 = 229 / 2 = 114.5 mm (half-flange for I-section in flexure) b/t = 114.5 / 19.6 = 5.84
Limits for F_y = 350 MPa:
Class 1: b/t ≤ 145/√350 = 7.75
Class 2: b/t ≤ 170/√350 = 9.09
5.84 < 7.75 → Class 1 flange ✓
Web classification (for flexure):
h = d - 2 × t_f = 612 - 2 × 19.6 = 572.8 mm h/w = 572.8 / 11.9 = 48.1
Limits for F_y = 350 MPa:
Class 1: h/w ≤ 1,100/√350 = 58.8
Class 2: h/w ≤ 1,700/√350 = 90.9
48.1 < 58.8 → Class 1 web ✓
Overall classification:
Both flange and web are Class 1. The section is Class 1 and can develop the full plastic moment with adequate rotation capacity.
Step 4 — Flexural Resistance (Cl. 13.5, 13.6)
Plastic moment capacity:
M_p = Z_x × F_y = 3,330 × 10³ × 350 / 10⁶ = 1,165.5 kN·m
φ × M_p = 0.90 × 1,165.5 = 1,049.0 kN·m
Check lateral-torsional buckling:
First, determine if LTB governs. The limiting unbraced length L_u:
r_t = radius of gyration of compression flange + 1/3 web in compression For doubly symmetric I-section: r_t ≈ r_y for simplification
L_u = 0.68 × sqrt(E/F_y) × r_y ≈ 1.1 × r_y × sqrt(E/F_y)
L_u = 1.1 × 49.8 × sqrt(200,000 / 350) = 1.1 × 49.8 × 23.9 = 1,309 mm = 1.31 m
Actual unbraced length L_b = 2.67 m > L_u = 1.31 m → LTB check required.
Elastic LTB moment (Cl. 13.6.5):
For W610x125:
- I_y = 39.5 × 10⁶ mm⁴ (weak axis moment of inertia)
- J = 1,230 × 10³ mm⁴ (Saint-Venant torsional constant)
- C_w = 2,990 × 10⁹ mm⁶ (warping constant)
L_b = 2,670 mm
M_u = ω₂ × (π/L_b) × sqrt(E × I_y × G × J + (π × E / L_b)² × I_y × C_w)
ω₂ = 1.14 (uniformly distributed load over the span, simple supports — from Table 3-2, CISC Handbook)
First term: E × I_y × G × J = 200,000 × 39.5 × 10⁶ × 77,000 × 1,230 × 10³ = 200,000 × 39.5 × 10⁶ × 77,000 × 1,230 × 10³ = 200,000 × 77,000 × 39.5 × 1,230 × 10⁹ = 1.54 × 10¹⁰ × 4.859 × 10⁴ × 10⁹ = 7.48 × 10²³ N²·mm⁶
Second term: (π × E / L_b)² × I_y × C_w = (π × 200,000 / 2,670)² × 39.5 × 10⁶ × 2,990 × 10⁹ = (235.5)² × 39.5 × 2,990 × 10¹⁵ = 55,460 × 1.181 × 10²⁰ = 6.55 × 10²⁴ N²·mm⁶
Combined: 7.48 × 10²³ + 6.55 × 10²⁴ = 7.30 × 10²⁴
sqrt(7.30 × 10²⁴) = 2.70 × 10¹² N·mm³
M_u = 1.14 × (π / 2,670) × 2.70 × 10¹² = 1.14 × 0.001177 × 2.70 × 10¹² = 3.62 × 10⁹ N·mm = 3,620 kN·m
Check LTB resistance:
0.67 × M_p = 0.67 × 1,165.5 = 780.9 kN·m
M_u = 3,620 kN·m > 780.9 kN·m → inelastic LTB region applies:
M_r = 1.15 × φ × M_p × (1 - 0.28 × M_p / M_u)
= 1.15 × 1,049.0 × (1 - 0.28 × 1,165.5 / 3,620) = 1,206.4 × (1 - 0.0902) = 1,206.4 × 0.9098 = 1,097.4 kN·m
BUT M_r cannot exceed φ × M_p = 1,049.0 kN·m
Therefore: M_r = 1,049.0 kN·m
Check:
M_f / M_r = 324.5 / 1,049.0 = 0.309 ✓ — Flexure is adequate with significant reserve.
Step 5 — Shear Resistance (Cl. 13.4)
Web slenderness for shear:
h/w = 48.1 Limit for shear buckling: 439 × sqrt(k_v / F_y) where k_v = 5.34 (unstiffened web)
439 × sqrt(5.34 / 350) = 439 × 0.1235 = 54.2
48.1 < 54.2 → Shear buckling does not govern. Use basic shear equation.
Shear resistance:
V_r = φ × 0.60 × F_y × d × t_w
= 0.90 × 0.60 × 350 × 612 × 11.9 / 1,000 = 0.90 × 0.60 × 350 × 7,283 / 1,000 = 1,377 kN
Check:
V_f / V_r = 162.2 / 1,377 = 0.118 ✓ — Shear is not critical for this W-shape under uniform loading.
Step 6 — Deflection Check (Serviceability)
Live load deflection (governs per NBCC):
w_L = 16.0 kN/m (unfactored)
δ_LL = 5 × w_L × L⁴ / (384 × E × I_x)
= 5 × 16.0 × (8,000)⁴ / (384 × 200,000 × 908 × 10⁶)
= 5 × 16.0 × 4.096 × 10¹⁵ / (384 × 200,000 × 908 × 10⁶)
= 3.277 × 10¹⁷ / 6.973 × 10¹³
= 4,700 mm⁴ · kN/m² / mm⁴... Let me recalculate carefully.
= 5 × 16.0 × 4,096 × 10¹² / (384 × 200,000 × 908 × 10⁶)
= 5 × 16.0 × 4.096 × 10¹⁵¹⁴... let me be precise:
5 × 16.0 = 80 80 × 8,000⁴ = 80 × 4.096 × 10¹⁵ = 3.277 × 10¹⁷
384 × E × I = 384 × 200,000 × 908 × 10⁶ = 384 × 1.816 × 10¹⁴ = 6.973 × 10¹⁶
δ_LL = 3.277 × 10¹⁷ / 6.973 × 10¹⁶ = 4.70 mm × (kN/m → N/mm)...
Actually, careful with units: w = 16.0 kN/m = 16.0 N/mm L = 8,000 mm E = 200,000 N/mm² I = 908 × 10⁶ mm⁴
δ_LL = 5 × 16.0 × 8,000⁴ / (384 × 200,000 × 908 × 10⁶)
5 × 16 = 80 80 × 8,000⁴ = 80 × 4.096 × 10¹⁵ = 3.277 × 10¹⁷ N·mm³
384 × 200,000 = 76,800,000 76,800,000 × 908 × 10⁶ = 6.973 × 10¹⁶ N·mm²
δ_LL = 3.277 × 10¹⁷ / 6.973 × 10¹⁶ = 4.70 mm
Allowable live load deflection:
L / 360 = 8,000 / 360 = 22.2 mm
δ_LL = 4.70 mm < 22.2 mm ✓ — Live load deflection is well within limits.
Total load deflection (SLS-1):
w_total = 13.25 + 16.0 = 29.25 kN/m (unfactored)
δ_total = δ_LL × (29.25 / 16.0) = 4.70 × 1.828 = 8.59 mm
L / 240 = 8,000 / 240 = 33.3 mm
8.59 mm < 33.3 mm ✓ — Total load deflection is adequate.
Step 7 — Lateral Bracing Requirements (Cl. 13.6.2)
Bracing spacing:
Maximum bracing spacing for Class 1 sections (Cl. 13.6.2):
L_b_max = 0.86 × r_y × sqrt(E / F_y) × (M_p / M_f) for segments with moment gradient
For the end segment (simple support to first brace at 2.67 m): Moment at brace = w × x × (L - x) / 2 where x = 2.67 m M_at_brace = 40.56 × 2.67 × (8.0 - 2.67) / 2 = 40.56 × 2.67 × 5.33 / 2 = 288.7 kN·m
M_p / M_at_brace = 1,165.5 / 288.7 = 4.04
L_b_max = 0.86 × 49.8 × sqrt(200,000 / 350) × 4.04 = 0.86 × 49.8 × 23.9 × 4.04 = 4,134 mm = 4.13 m
The actual bracing spacing (2.67 m) is less than the maximum (4.13 m) → OK.
However, for compactness in design, the actual bracing spacing of 2.67 m already satisfies L_u (1.31 m) check completed above, and the LTB check confirmed the section is adequate.
Step 8 — Final Check Summary
| Check | Demand | Capacity | Ratio | Status |
|---|---|---|---|---|
| Flexure (M_r) | 324.5 kN·m | 1,049.0 kN·m | 0.31 | ✓ |
| Shear (V_r) | 162.2 kN | 1,377 kN | 0.12 | ✓ |
| Live load deflection | 4.70 mm | 22.2 mm | 0.21 | ✓ |
| Total deflection | 8.59 mm | 33.3 mm | 0.26 | ✓ |
| LTB (M_r) | 324.5 kN·m | 1,049.0 kN·m | 0.31 | ✓ |
Selected section: W610x125 (Grade 350W) with intermediate bracing at 2.67 m spacing.
Design Optimisation
The W610x125 is conservatively sized (31% flexural utilisation). A lighter section could be considered if deflection does not govern:
Try W530x92 (US equivalent W21x62):
- Z_x = 2,300 × 10³ mm³
- φ × M_p = 0.90 × 2,300 × 350 / 1,000 = 724.5 kN·m
- M_f = 324.5 kN·m → ratio = 0.45
Deflection check: I_x for W530x92 = 552 × 10⁶ mm⁴ δ_LL = 4.70 × (908 / 552) = 7.73 mm < 22.2 mm ✓
LTB check (L_b = 2.67 m): r_y = 50.1 mm (similar to W610x125) LTB resistance likely adequate for this short unbraced length.
W530x92 would be adequate with 45% flexural utilisation. The W610x125 was selected to demonstrate the full design procedure for a heavier section, but W530x92 would be more economical in practice.
Related Pages
- Canada CSA S16 Steel Design Guide — Full CSA S16 design reference
- CSA S16 Column Design — Worked Example — Step-by-step column design example
- CSA S16 Column Buckling — Euler & Fcr Curves — Column buckling theory
- CSA S16 Beam Design — Flexure, LTB & Shear — Detailed beam design guide
- Canadian Steel Beam Sizes — W Shapes, HSS — Complete section tables
- Canadian Steel Grades — G40.21 300W to 480W — Material properties
- CSA S16 Load Combinations — NBCC ULS & SLS — Canadian load combination guide
- BEAM Capacity Calculator — Free multi-code beam calculator
Frequently Asked Questions
When should intermediate lateral bracing be provided for a steel beam?
Intermediate lateral bracing is required when the unbraced length L_b exceeds the limiting unbraced length L_u. For a W610x125 in 350W, L_u ≈ 1.31 m. Without intermediate bracing, the full 8.0 m span would require an LTB check with ω₂ = 1.14 and L = 8.0 m, resulting in a much lower M_r. For this example, bracing at 2.67 m (one-third points) ensures the beam can develop its full plastic moment. In practice, steel deck with puddle welds at ~300 mm spacing provides continuous lateral restraint to the top (compression) flange, eliminating the need for separate bracing. Unbraced beams (such as crane girders or exposed roof beams) require explicit LTB verification.
How do I check combined bending and shear per CSA S16?
CSA S16 Clause 14.6 requires interaction checks when V_f exceeds 60% of V_r. The interaction equation is: M_f / M_r + 0.6 × V_f / V_r ≤ 1.33 for V_f / V_r > 0.6. In this worked example, V_f / V_r = 0.118, far below the 0.6 threshold. Shear rarely governs for standard W-shape beams under uniform loading — the interaction check is typically only relevant for beams with heavy concentrated loads near supports (transfer beams, crane girders, and deep plate girders with thin webs). For plate girders (h/w > 440/sqrt(F_y)), the shear resistance may be governed by post-buckling tension field action per Cl. 14.4, and combined bending and shear must always be checked per Cl. 14.5.
What live load deflection limit does NBCC 2020 specify for floors?
NBCC 2020 does not prescribe specific deflection limits — these are established by the engineer of record based on occupancy requirements and industry practice. The commonly used L/360 for live load deflection of floor beams comes from the CSA S16 Commentary (Appendix D) and industry standards. More stringent limits may apply: L/480 for floors with brittle finishes (terrazzo, stone tile, thin-set ceramic), L/600 for vibration-sensitive occupancies (laboratories, operating rooms, gymnasia). The Canadian Sheet Steel Building Institute (CSSBI) provides additional guidance for steel deck floor vibration criteria. For this office beam example, L/360 is appropriate for the 325 Pa partition load allowance.
How is the moment gradient factor ω₂ determined for Canadian beam design?
CSA S16 references ω₂ from Table 3-2 of the CISC Handbook of Steel Construction. The factor accounts for the shape of the bending moment diagram along the unbraced segment: ω₂ = 1.00 for uniform moment (worst case), 1.14 for uniformly distributed load on a simple span, 1.35 for a central point load, and up to 1.75 for double curvature bending (equal and opposite end moments). The ω₂ factor in CSA S16 is conceptually identical to AISC's C_b factor but uses slightly different reference values. Unlike AISC, CSA S16 provides ω₂ in a single table rather than a formula, making it simpler to use. For segments with linear moment gradient, ω₂ can be calculated as 1.75 + 1.05β + 0.3β² where β = |M₁|/|M₂| ≤ 1.0 at the segment end with the smaller-to-larger moment ratio.
This page is for educational reference. Beam design per CSA S16-19 and NBCC 2020. Verify section properties against current CISC Handbook of Steel Construction. Results are PRELIMINARY — NOT FOR CONSTRUCTION without independent P.Eng. verification.