UK Shear Stud Design — EN 1994-1-1 Headed Stud Capacity Table

Design resistance of headed shear studs for composite steel-concrete beams per BS EN 1994-1-1:2004 Clause 6.6 with UK National Annex. Capacity tables (PRd) for standard 19 mm and 22 mm diameter studs in solid slabs and composite decks, reduction factors for profiled steel sheeting, and a design example for a UK composite beam.

Quick access: UK Steel Grades | UK Steel Properties | UK Beam Sizes | UK Bolt Capacity | All UK References


Shear Stud Design per EN 1994-1-1 Clause 6.6

The design shear resistance of a headed stud in a solid slab is the lesser of:

Stud failure (steel): PRd = 0.8 × fu × π × d²/4 / γVs

Concrete failure (crushing): PRd = 0.29 × α × d² × √(fck × Ecm) / γVs

Where:

Stud Capacity Table — Solid Slab

Stud Diameter Stud Height (mm) Steel Grade fu (MPa) PRd — Steel (kN) PRd — C30/37 (kN) PRd — Design (kN)
19 mm 100 S235J2+C450 450 81.6 79.3 79.3
19 mm 100 S235J2+C450 450 81.6 86.8 (C40/50) 81.6 (stud governs)
19 mm 125 S235J2+C450 450 81.6 79.3 79.3
22 mm 100 S235J2+C450 450 109.4 106.3 106.3
22 mm 125 S235J2+C450 450 109.4 106.3 106.3
22 mm 150 S235J2+C450 450 109.4 106.3 106.3

Reduction Factor for Profiled Steel Sheeting

For composite slabs with profiled steel decking, the stud capacity is reduced by factor kt:

Ribs perpendicular to beam: kt = 0.6 × (b0/hp) × (hsc/hp − 1) ≤ 1.0

Ribs parallel to beam: kt = 0.6 × (b0/hp) × (hsc/hp − 1) ≤ 1.0 (similar expression with different geometry)

Where:

Typical Reduction Factors for UK Composite Deck Profiles

Deck Profile hp (mm) b0 (mm) 19×100 mm Stud kt 19×125 mm Stud kt
50 mm trapezoidal 50 90 0.96 1.0
60 mm trapezoidal 60 90 0.86 1.0
80 mm re-entrant 80 120 0.60 0.86
100 mm deep deck 100 130 0.78

Worked Example — Composite Beam with 19 mm Studs

Beam details:

Step 1 — Stud Capacity

PRd (solid slab) = 79.3 kN (governed by concrete for C30/37) kt = 0.6 × (90/60) × (100/60 − 1) = 0.6 × 1.5 × 0.667 = 0.60 (≤ 1.0)

PRd (deck) = 0.60 × 79.3 = 47.6 kN per stud

Step 2 — Number of Studs Required

Assume total longitudinal shear force: VL = min(0.85 × Ac × fck/γc, Aa × fy/γMa) = between concrete crushing and steel yielding.

For full shear connection:

VL = Aa × fy/γMa = 131 × 10² × 355 / 1.0 = 4,651 kN (steel governs)

Number of studs required each side of midspan: n = VL / (2 × PRd per stud) = 4,651 / (2 × 47.6) = 48.9 ≈ 50 studs

With 2 studs per rib at 300 mm spacing: 2 × (8,000/300) = 53 studs — adequate (with 2 per side for end detailing).

Step 3 — Degree of Shear Connection

η = n_actual / n_full = 53/50 = 1.06 ≥ 1.0 → Full shear connection.

For partial shear connection (< 1.0), the moment resistance is reduced per EN 1994-1-1 Clause 6.2.1.3.

Design Guidance


Design Resources


Frequently Asked Questions

What is the design resistance of a 19 mm shear stud in a solid C30/37 slab?

The design resistance PRd for a 19 mm headed stud (fu = 450 MPa, hsc ≥ 4d = 76 mm) in a solid C30/37 slab is: minimum of steel failure (0.8 × 450 × π × 19²/4 / 1.25 = 81.6 kN) and concrete failure (0.29 × 1.0 × 19² × √(30 × 33,000) / 1.25 = 79.3 kN). The design resistance is PRd = 79.3 kN (governed by concrete crushing). For C40/50 concrete, PRd = 86.8 kN (governed by stud strength at 81.6 kN).

What is the reduction factor for studs in profiled steel decking?

The reduction factor kt per EN 1994-1-1 Clause 6.6.4 accounts for the reduced concrete confinement in profiled deck ribs. For 19 × 100 mm studs in a 60 mm trapezoidal deck (b0 = 90 mm): kt = 0.6 × (90/60) × (100/60 − 1) = 0.60. The stud capacity reduces from 79.3 kN to 47.6 kN. For 19 × 125 mm studs in the same deck: kt = 0.6 × (90/60) × (125/60 − 1) = 0.975 ≈ 1.0 (full capacity achieved). Longer studs significantly improve efficiency in profiled decks.

What γVs value does the UK NA specify for shear studs?

The UK NA to BS EN 1994-1-1 specifies γVs = 1.25 for shear studs. This is the same as the recommended value. The factor applies to both the stud steel failure and concrete failure terms in the PRd formula. The UK NA also confirms that the limiting tensile strength fu = 450 MPa for standard EN ISO 13918 studs (type SD1).

What is the standard shear stud specification for UK composite beams?

The standard UK specification for shear studs is: 19 mm diameter × 100 mm long, grade S235J2+C450 per EN ISO 13918 (type SD1, fu = 450 MPa minimum, Charpy 27 J at -20°C). For deeper composite slabs or where higher capacity is needed, 22 mm × 125 mm studs are used. Studs are through-deck welded to the beam top flange using a drawn-arc welding process per BS EN 1090-2. The minimum flange thickness for 19 mm stud welding is 8 mm.


Related Pages


Educational reference only. All design values are per BS EN 1993-1-1:2005 + UK National Annex and BS EN 10025-2:2019. Verify all values against the current editions of the standards and the applicable National Annex for your project jurisdiction. Designs must be independently verified by a Chartered Structural Engineer registered with the Institution of Structural Engineers (IStructE) or the Institution of Civil Engineers (ICE). Results are PRELIMINARY — NOT FOR CONSTRUCTION without independent professional verification.