Property Value Unit
Depth (d) 490.2 mm
Flange Width (bf) 284.5 mm
Flange Thickness (tf) 30.5 mm
Web Thickness (tw) 17.0 mm
Cross-Sectional Area (A) 247.1 cm²
Mass 193.4 kg/m

Elastic Section Properties (Metric)

Property Strong Axis (X-X) Weak Axis (Y-Y) Unit
Moment of Inertia (I) 102,393 11,571 cm⁴
Elastic Section Modulus (S) 4,195 818 cm³
Plastic Section Modulus (Z) 4,752 1,257 cm³
Radius of Gyration (r) 20.40 6.86 cm

Torsional Properties

Property Value Unit
Torsional Constant (J) 604 cm⁴
Warping Constant (Cw) 6,094,950 cm⁶
Distance Between Flange Centroids (ho) 45.97 cm
Effective Radius (rts) 7.95 cm

Imperial Reference

Property Value Unit
Depth (d) 19.30 in
Flange Width (bf) 11.20 in
Area (A) 38.30 in²
Weight 130 lb/ft

Section Profile Summary

With Ix = 102,393 cm⁴, this wide flange is appropriate for long-span floor beams and transfer girders where stiffness controls the design.

At 490.2 mm deep, this section is common for floor beams, portal frame rafters, and columns in commercial and industrial buildings.

Key Design Checks (CSA S16)

Check Formula This Section
Plastic moment Mp = Zx × Fy 1,663 kN·m
Deflection Δ = 5wL⁴/(384EIx) Use Ix = 102,393 cm⁴
Torsion St. Venant = GJ/L J = 604 cm⁴
Column buckling KL/r → Fcr r_x = 20.4 cm

Design Notes

Verification (CSA S16): All designs using this section must be verified by a licensed Professional Engineer. Before finalizing member selection, check beam-column interaction (P-M), lateral-torsional buckling, serviceability deflections, and all connection limit states. See Engineering Disclaimer.

Worked Example: School classroom beam — w460x193

Scenario: School building — tighter deflection limit for suspended ceiling integrity. Simply supported wide flange, 8.3 m span, 2.4 m tributary width. Service loads: 3.5 kPa dead + 3.0 kPa live (15.6 kN/m total).

Given:

Step 1 — Live load deflection:

Δ_LL = 5 w_L L⁴ / (384 E Ix)

Δ_LL = 5 × 7.2 × (8333)⁴ / (384 × 200000 × 1,023,930,000)

Δ_LL = 2.2 mm

Step 2 — Deflection limit (L/360):

Δ_limit = L / 360 = 8333 / 360 = 23.1 mm

Step 3 — Dead + live deflection:

Δ_total = 4.8 mm

Step 4 — Design check:

✓ Live load deflection is within the L/360 limit.

Verify the design moment M*_Ed (from factored loads 1.35G + 1.5Q per CSA S16) does not exceed φMn = 1,497 kN·m. Also confirm shear resistance and bearing details at the supports.