W24X370 Steel Beam — Section Properties

Dimensions

Property Value Unit
Depth (d) 28 in (711.2 mm)
Flange Width (bf) 13.70 in (348.0 mm)
Flange Thickness (tf) 2.72 in
Web Thickness (tw) 1.52 in
Area (A) 109 in² (703.3 cm²)
Weight 370 lb/ft (551 kg/m)

Elastic Section Properties

Property Strong Axis (X-X) Weak Axis (Y-Y) Unit
Moment of Inertia (I) 13,400 1,160 in⁴
Elastic Section Modulus (S) 957 170 in³
Plastic Section Modulus (Z) 1,130 267 in³
Radius of Gyration (r) 11.10 3.27 in

Torsional Properties

Property Value Unit
Torsional Constant (J) 201 in⁴
Warping Constant (Cw) 186,000 in⁶
Distance Between Flange Centroids (ho) 25.30 in
Effective Radius (rts) 3.92 in

Section Profile Summary

With Ix = 13,400 in⁴, this wide flange is well-suited for long-span floor beams and transfer girders where stiffness controls the design.

At 28" deep, this section is frequently specified for primary floor beams, girders, and moment frame columns in commercial and institutional buildings.

Key Design Checks (AISC 360)

Check Formula This Section
Plastic moment Mp = Zx × Fy 56,500 kip-in
Deflection Δ = 5wL⁴/(384EIx) Use Ix = 13,400 in⁴
Torsion St. Venant = GJ/L J = 201 in⁴
Column buckling KL/r → Fcr r_x = 11.1 in

Design Notes

Verification (AISC 360): All designs using this section must be verified by a licensed Professional Engineer. Before finalizing member selection, check beam-column interaction (P-M), lateral-torsional buckling, serviceability deflections, and all connection limit states. See Engineering Disclaimer.

Worked Example: Light commercial floor beam — w24x370

Scenario: Retail space floor — higher live load for public occupancy. Simply supported wide flange, 60 ft span, 8 ft tributary width. Service loads: 55 psf dead + 60 psf live (920 plf total).

Given:

Step 1 — Live load deflection check:

Δ_LL = 5 w_L L⁴ / (384 E Ix)

Δ_LL = 5 × (480/12) × (720)⁴ / (384 × 29,000,000 × 13,400)

Δ_LL = 0.36 in

Step 2 — Allowable deflection (IBC Table 1604.3, L/240):

Δ_allow = L / 240 = 720 / 240 = 3.00 in

Step 3 — Dead + live deflection:

Δ_total = 0.69 in

Step 4 — Design check:

✓ Live load deflection is within the L/240 limit.

The required flexural strength at ultimate is approximately w_u L²/8. With factored loads 1.2D + 1.6L, verify φMn = 4,238 kip-ft is adequate per AISC 360 Chapter F. Also check shear capacity (φVn = 0.6 Fy Aw × 0.9) and bearing at supports.

Related Resources

Design Resources


Educational reference only. Verify all section properties against the current AISC 360 Manual and mill certificates before design. Results are PRELIMINARY — NOT FOR CONSTRUCTION.