Design Problem
Problem: Verify a simply supported 533UB in S355 steel spanning L = 6.0 m between supports. The beam supports a composite floor slab that provides full lateral restraint to the top (compression) flange.
Loading:
- Permanent action (dead): gk = 12.0 kN/m (slab + finishes + services + beam self-weight)
- Variable action (imposed): qk = 20.0 kN/m (office occupancy, EN 1991-1-1 Category B)
Design to BS EN 1993-1-1 with UK NA:
- ÃÂóM0 = 1.00, ÃÂóM1 = 1.00, ÃÂóM2 = 1.25 (UK NA)
- Steel: S355JR (EN 10025-2), fy = 355 MPa for t âÃÂä 16 mm, fu = 470 MPa
- UK NA combination: 1.35 ÃÂÃÂ Gk + 1.5 ÃÂÃÂ Qk (Eq. 6.10b)
Section Properties — 533UB
From SCI P363 (Blue Book) for UK sections:
| Property | Symbol | Value | Units |
|---|---|---|---|
| Depth | h | 529 | mm |
| Flange width | b | 211 | mm |
| Web thickness | tw | 10.2 | mm |
| Flange thickness | tf | 15.6 | mm |
| Root radius | r | 12.7 | mm |
| Area | A | 131 | cmÃÂò |
| Iy | Iy | 65,750 | cmâÃÂô |
| Iz | Iz | 2,450 | cmâÃÂô |
| Wpl,y | Wpl,y | 3,040 | cmÃÂó |
| Wel,y | Wel,y | 2,486 | cmÃÂó |
| Iw | Iw | 1.24 | dmâÃÂö |
| It | It | 126 | cmâÃÂô |
| Mass | m | 103 | kg/m |
fy = 345 MPa for flange (tf = 15.6 âÃÂä 16 mm — actual tf < 16, so fy = 355 MPa). Wait: tf = 15.6 mm âÃÂä 16 mm, so fy = 355 MPa.
Design Loads and Internal Forces
ULS Combination (UK NA Eq. 6.10b)
wEd = 1.35 ÃÂÃÂ 12.0 + 1.5 ÃÂÃÂ 20.0 = 16.2 + 30.0 = 46.2 kN/m
Maximum bending moment: My,Ed = wEd ÃÂàLÃÂò / 8 = 46.2 ÃÂà6.0ÃÂò / 8 = 207.9 kNÃÂ÷m
Maximum shear force: VEd = wEd ÃÂÃÂ L / 2 = 46.2 ÃÂÃÂ 6.0 / 2 = 138.6 kN
Cross-Section Classification (Clause 5.5)
ÃÂõ = âÃÂÃÂ(235/fy) = âÃÂÃÂ(235/355) = 0.814
Flange (outstand in compression)
c = (b âÃÂàtw âÃÂà2r) / 2 = (211 âÃÂà10.2 âÃÂà25.4) / 2 = 175.4 / 2 = 87.7 mm
c/tf = 87.7 / 15.6 = 5.62
Class 1 limit: c/tf âÃÂä 9ÃÂõ = 9 ÃÂà0.814 = 7.33
5.62 âÃÂä 7.33 âÃÂàFlange is Class 1
Web (internal in bending)
cw = h âÃÂà2tf âÃÂà2r = 529 âÃÂà31.2 âÃÂà25.4 = 472.4 mm
cw/tw = 472.4 / 10.2 = 46.3
Class 1 limit (pure bending): cw/tw âÃÂä 72ÃÂõ = 72 ÃÂà0.814 = 58.6
46.3 âÃÂä 58.6 âÃÂàWeb is Class 1
Result: 533UB in S355 is Class 1 — plastic design is permitted.
Bending Moment Resistance (Clause 6.2.5)
Mc,Rd = Wpl,y ÃÂàfy / ÃÂóM0 = 3,040 ÃÂà10ÃÂó ÃÂà355 / 1.00 = 1,079 ÃÂà10âÃÂö NÃÂ÷mm = 1,079 kNÃÂ÷m
Utilisation: My,Ed / Mc,Rd = 207.9 / 1,079 = 0.193 — OK (19 % utilised)
The 533UB in S355 has substantial reserve capacity for this span and loading, as expected for a deep UB section at 6.0 m. This suggests a lighter section could be considered.
Shear Resistance (Clause 6.2.6)
Av = A âÃÂà2btf + (tw + 2r)tf = 13,100 âÃÂà2ÃÂÃÂ211ÃÂÃÂ15.6 + (10.2 + 25.4)ÃÂÃÂ15.6
Av = 13,100 âÃÂà6,583 + 35.6ÃÂÃÂ15.6 = 6,517 + 555 = 7,072 mmÃÂò
Min Av = ÃÂ÷ hw tw = 1.0 ÃÂà(529 âÃÂà31.2) ÃÂà10.2 = 1.0 ÃÂà497.8 ÃÂà10.2 = 5,078 mmÃÂò
Av = 7,072 âÃÂÃÂ¥ 5,078 — OK
Vpl,Rd = Av ÃÂàfy / (âÃÂÃÂ3 ÃÂàÃÂóM0) = 7,072 ÃÂà355 / (1.732 ÃÂà1.00) = 2,510,560 / 1.732 = 1,449 kN
Utilisation: VEd / Vpl,Rd = 138.6 / 1,449 = 0.096 — OK (10 % utilised)
VEd / Vpl,Rd < 0.50 âÃÂàNo bending-shear interaction required per Clause 6.2.8(2).
Lateral-Torsional Buckling (Clause 6.3.2)
Condition 1 — In-service (composite slab provides continuous compression flange restraint)
No LTB check required. Mc,Rd = 1,079 kNÃÂ÷m governs.
Condition 2 — Construction stage (beam alone, lateral restraint at supports only, span 6.0 m)
Mcr for simply supported beam under UDL (C1 = 1.13 for UDL, kz = kw = 1.0):
Mcr = C1 ÃÂàÃÂÃÂÃÂòEIz / LÃÂò ÃÂàâÃÂÃÂ(Iw/Iz + LÃÂòGIt / (ÃÂÃÂÃÂòEIz))
Mcr = 1.13 ÃÂàÃÂÃÂÃÂò ÃÂà210,000 ÃÂà2,450ÃÂÃÂ10âÃÂô / 6,000ÃÂò ÃÂàâÃÂÃÂ(1.24ÃÂÃÂ10ÃÂùÃÂò/2,450ÃÂÃÂ10âÃÂô + 6,000ÃÂòÃÂÃÂ81,000ÃÂÃÂ126ÃÂÃÂ10âÃÂô/(ÃÂÃÂÃÂòÃÂÃÂ210,000ÃÂÃÂ2,450ÃÂÃÂ10âÃÂô))
= 1.13 ÃÂà2.069ÃÂÃÂ10âÃÂö ÃÂà2.450ÃÂÃÂ10âÃÂ÷ / 3.6ÃÂÃÂ10âÃÂ÷ ÃÂàâÃÂÃÂ(50,612 + 1.296ÃÂÃÂ10ÃÂùâÃÂô ÃÂà8.1ÃÂÃÂ10âÃÂô ÃÂà1.26ÃÂÃÂ10âÃÂö / (2.069ÃÂÃÂ10âÃÂö ÃÂà2.45ÃÂÃÂ10âÃÂ÷))
= 1.13 ÃÂà1.408ÃÂÃÂ10âÃÂö ÃÂàâÃÂÃÂ(50,612 + 1.323ÃÂÃÂ10ÃÂòâÃÂô / 5.069ÃÂÃÂ10ÃÂùÃÂó)
= 1.590ÃÂÃÂ10âÃÂö ÃÂàâÃÂÃÂ(50,612 + 26,099)
= 1.590ÃÂÃÂ10âÃÂö ÃÂàâÃÂÃÂ(76,711)
= 1.590ÃÂÃÂ10âÃÂö ÃÂà277 = 440ÃÂÃÂ10âÃÂö NÃÂ÷mm = 440 kNÃÂ÷m
ÃÂûLT,bar = âÃÂÃÂ(Wpl,y fy / Mcr) = âÃÂÃÂ(1,079ÃÂÃÂ10âÃÂö / 440ÃÂÃÂ10âÃÂö) = âÃÂÃÂ2.452 = 1.566
For h/b = 529/211 = 2.51 > 2.0 âÃÂàbuckling curve c (ÃÂñLT = 0.49)
ÃÂæLT = 0.5 ÃÂà[1 + 0.49 ÃÂà(1.566 âÃÂà0.2) + 1.566ÃÂò] = 0.5 ÃÂà[1 + 0.669 + 2.452] = 0.5 ÃÂà4.121 = 2.061
ÃÂÃÂLT = 1 / [2.061 + âÃÂÃÂ(2.061ÃÂò âÃÂà1.566ÃÂò)] = 1 / [2.061 + 1.339] = 1 / 3.400 = 0.294
Mb,Rd = ÃÂÃÂLT ÃÂàWpl,y ÃÂàfy / ÃÂóM1 = 0.294 ÃÂà1,079 = 317 kNÃÂ÷m
Construction stage moment (beam + wet concrete âÃÂà12.0 kN/m): MEd,c = 1.35 ÃÂà12.0 ÃÂà6.0ÃÂò / 8 = 73.0 kNÃÂ÷m
Utilisation: 73.0 / 317 = 0.230 — OK (23 %)
The 533UB is adequate for both in-service and construction conditions.
Serviceability Deflection Check
SLS imposed load: wSLS = qk = 20.0 kN/m
ÃÂô = 5wLâÃÂô / (384EIy) = 5 ÃÂà20.0 ÃÂà6,000âÃÂô / (384 ÃÂà210,000 ÃÂà65,750ÃÂÃÂ10âÃÂô)
= 5 ÃÂà20.0 ÃÂà1.296ÃÂÃÂ10ÃÂùâÃÂõ / (384 ÃÂà210,000 ÃÂà6.575ÃÂÃÂ10ÃÂùÃÂù)
= 1.296ÃÂÃÂ10ÃÂùâÃÂ÷ / (5.302ÃÂÃÂ10ÃÂùâÃÂù) = 6.1 mm
L/360 = 6,000/360 = 16.7 mm âÃÂà6.1 < 16.7 — OK (37 % utilised)
Total deflection (gk + qk = 32.0 kN/m): ÃÂôtot = 6.1 ÃÂà32.0/20.0 = 9.8 mm
L/200 = 30.0 mm âÃÂà9.8 < 30.0 — OK
Summary
| Check | Resistance | Demand | Utilisation | Status |
|---|---|---|---|---|
| Bending Mc,Rd | 1,079 kNÃÂ÷m | 207.9 kNÃÂ÷m | 0.19 | OK |
| Shear Vpl,Rd | 1,449 kN | 138.6 kN | 0.10 | OK |
| LTB construction | 317 kNÃÂ÷m | 73.0 kNÃÂ÷m | 0.23 | OK |
| Deflection L/360 | 16.7 mm | 6.1 mm | 0.37 | OK |
Conclusion: 533UB in S355 is adequate for the 6.0 m span with significant reserve capacity. A lighter section (e.g., 457UB or 406UB) could be considered for optimisation.
Design Resources
- UK Steel Grades Reference — EN 10025-2 grade selection for UK projects
- UK Steel Mechanical Properties — fy, fu, and elongation tables
- UK Universal Beam and Column Sizes — UB/UC section dimensions and properties
- UK Bolt Capacity Tables — Class 8.8 and 10.9 bolt resistance
- UK Beam Design Guide — EN 1993-1-1 flexure, shear, and LTB
- UK Connection Design Guide — EN 1993-1-8 bolted and welded joints
- All UK Steel Design References — complete library
Try Our Free Calculator
Check your UK beam design with our free UK Beam Capacity Calculator — full derivation, code clause references, instant results.
Open UK Beam Capacity Calculator âÃÂÃÂ
Frequently Asked Questions
What is the maximum span for a 533UB in S355?
The maximum span depends on loading, restraint conditions, and deflection limits. For a typical office floor loading (5.0 kN/mÃÂò imposed, 3.0 m tributary), a 533UB in S355 can span approximately 10-12 m before LTB governs at the construction stage or deflection exceeds L/200. At 6.0 m, the 533UB is lightly utilised at 19 % in bending. At 9.0 m, utilisation increases to approximately 40-50 % in bending and 60-70 % in construction-stage LTB, with deflection likely governing at approximately 20 mm for imposed load.
What lateral restraint is required for UK UB beams during construction?
The UK Building Regulations and BS EN 1090-2 require that steel beams during construction have adequate lateral restraint. For the 533UB with h/b = 2.51, LTB check at the construction stage shows Mb,Rd = 317 kNÃÂ÷m, which is 3.3ÃÂàthe construction moment. For beams with h/b > 2.0 at longer spans, intermediate restraint at third points or temporary propping is typically required. Permanent lateral restraint from the composite slab or secondary steelwork is the preferred solution.
How does the UK NA affect beam design compared to the recommended values?
The UK NA to BS EN 1993-1-1 adopts ÃÂóM0 = 1.00 (same as recommended). The main difference from some other EU National Annexes is the use of Eq. 6.10b for ULS combinations rather than the more onerous Eq. 6.10. The UK NA also adopts UK-specific section sizes (UB/UC series per BS 4-1) rather than European IPE/HEA sections. The design methodology is otherwise identical.
What is the utilisation of a 533UB at 6.0 m span?
At 6.0 m span with typical office loading (12 kN/m dead + 20 kN/m imposed), the 533UB in S355 is lightly utilised: 19 % in bending, 10 % in shear, 23 % in LTB, and 37 % in deflection. This suggests a 457UB or 406UB could be more economical. The deep 533UB is typically used for spans of 8-12 m in UK practice.
Related Pages
- EN 1993 Steel Design Overview
- European Steel Properties
- EN 1993 Beam Design Guide
- EN 1993 Column Buckling
- EN 1990 Load Combinations
- UK Steel Chemical Composition
- UK Steel Charpy Values
Educational reference only. All design values are per BS EN 1993-1-1:2005 + UK National Annex and BS EN 10025-2:2019. Verify all values against the current editions of the standards and the applicable National Annex for your project jurisdiction. Designs must be independently verified by a Chartered Structural Engineer registered with the Institution of Structural Engineers (IStructE) or the Institution of Civil Engineers (ICE). Results are PRELIMINARY — NOT FOR CONSTRUCTION without independent professional verification.